The output 1 is used to drive the main heater, The output 2 is used to
drive the cooling fan, the output 3 is used for end of profile relay and the
output 4 is used to drive the auxiliary heater.
Temperature
L
1000 C
L
400 C
0
Figure 5.2 Temperature profile of the Heat Treatment Oven
Figure 5.2 Temperature profile of the Heat Treatment Oven
The temperature profile is shown as Fig. 5.2. To achieve this profile,
the profiler is configured by the following setting:
Global Data
Global Data
STAR = PV
END = OFF
DLAY = 0
PFR =CONT
HBT = 0.05
Profile Data
Profile Data
PROF = 1
HBBD = 50
RMPU = HH.MM
DLLU = HH.MM
Segment Data
Segment Data
SGNO = 1
SGTY = RAMP
TGSP = 400.0
RTRR = 25
P2EV = 0000
HBTY = 1
Auto-tuning is performed at 400 C for
Auto-tuning
L
PID1 and 1000 C for PID2.
25
46
55
SGNO = 2
SGTY = DLL
P2EV = 0000
HBTY = 3
DLLT = 21
SGNO = 3
SGTY = RAMP
TGSP = 1000.0
RTRR = 9
P2EV = 1100
HBTY = 1
SGNO = 4
SGTY = DLL
P2EV = 1100
HBTY = 3
DLLT = 18
L
UM0P411A
73
88
SGNO = 5
SGTY = RAMP
TGSP = 25.0
RTRR = 15
P2EV = 0001
HBTY = 2
SGNO = 6
SGTY = END
CYCL = 1
FSP = 25.0
Controller Configuration Data
Controller Configuration Data
ALF2 = ENDP
A2MD = 0000
INPT = K_TC
OUT1 = HTPC
O1FT = BPLS
L
UNIT = C
DP = 1_DP
CYC1 = 18.0
Time
OUT2 = EVN1
OUT3 = ALM2
OUT4 = EVN3
OUT5 = REPV
OP5L = 0.0
OP5H = 100.0
REL5 = 0.0
REH5 = 1000.0
79