Help In The Case Of Faults; Fault List - Siemens Synco 200 Basic Documentation

Universal controllers rlu2
Hide thumbs Also See for Synco 200:
Table of Contents

Advertisement

Causes for faults
Legend
148 / 174
Siemens
Building Technologies
11

Help in the case of faults

11.1

Fault list

The following list contains all possible causes for faults, their display and priority.
Display
Error / fault cause
FROST
Frost hazard.
Type: Simple alarm, frost with frost
protection unit (parameter: NO)
Type: Extended alarm, frost with sensor
(parameter: YES or YES3)
MAINALM
1
Main controlled variable missing
Sequence controller 1
Type: Simple alarm
MAINALM
Main controlled variable missing
Sequence controller 2
Type: Simple alarm
DV ALM
1
Deviation message, sequence
controller 1
\_ : Lower deviation
_/ : Upper deviation
Type: Simple alarm
2
Deviation message, sequence
DV ALM
controller 2
\_ : Lower deviation
_/ : Upper deviation
Type: Simple alarm
Sensor error X1
X1 - - - / ooo
Type: Simple alarm
X2 - - - / ooo
Sensor error X2
Type: Simple alarm
X3 - - - / ooo
Sensor error X3
Type: Simple alarm
X4 - - - / ooo
Sensor error X4
Type: Simple alarm
X5 - - - / ooo
Sensor error X5
Type: Simple alarm
STATUS OK
Display in normal operation
Display
Meaning
- - -
Open circuit
ooo
Short-circuit
Universal Controllers RLU2...
Help in the case of faults
Priority
1
2
3
4
5
6
7
8
9
10
11
CE1P3101en
29.08.2008