Limit sensor
connected?
Configuration
Setting values
Siemens
Building Technologies
9.6.4
Troubleshooting
When you leave the commissioning menu, the universal controller checks whether
a sensor is connected to the LIM input.
If, at that time, a sensor is connected, but is missing later, a sensor error
•
message is delivered and presented on the display:
"Xx ---"
=> sensor missing
–
"Xx ooo"
=> short-circuit
–
If, at that time, no sensor is connected, limitation will be deactivated
•
9.6.5
Settings
Path:
... > COMMIS > CONF > CTLOOP 1 (type A)
Display
Name
STRATGY
Control strategy
Path:
... > COMMIS > CONF > CTLOOP 1 (type U)
Display
Name
LIM
General limit
controller
Path:
... > COMMIS > CONF > CTLOOP 2
Display
Name
LIM
General limit
controller
Path:
... > PARA > CTLOOP 1
... > PARA > CTLOOP 2
Display
Name
LIM MAX
Gen limiter limit
value high
LIM MIN
Gen limiter limit
value low
LIM DHI
Gen limiter
differential high
LIM DLO
Gen limiter
differential low
LIMCOOL
Reduction min
limitation cooling
LIM XP
Gen limiter P-band
Xp
LIM TN
Gen limiter integr
action time Tn
Universal Controllers RLU2...
Controller (CTLOOP x)
Range / comments
LIM (only type A)
Range / comments
Activation of general limitation; adjustable
values: ---, X1, X2, ... (nur analoge Werte)
(nur Typ U)
Range / comments
Activation of general limitation; adjustable
values: ---, X1, X2, ... (analog values only)
Range
Limit sensor input
range
Limit sensor input
range
0...500 K
0...500 K
0...10 K
0...500 K
00.00...60.00 m.s
Factory setting
35 °C
16 °C
50 K
50 K
0 K
15 K
02.00 m.s
123 / 174
CE1P3101en
29.08.2008