Configuration
Setting values
Display values
Wiring test
74 / 174
Siemens
Building Technologies
8.3.11 Settings
Path:
... > COMMIS > CONF > HREC
Display
Name
HREC
Mixing damper/HR
MECH 1
MECH input 1
MECH 2
MECH input 2
MAT
Mixed air temperature
IN X
Preselection external
COOLER
Cooling coil valve
Path:
... > PARA > HREC
Display
Name
TYPE
Type
MIN POS
Positioning signal min
MAX POS
Positioning signal max
MECHSET MECH limit value
STUP-TI
Startup time
MAT SP
Mixed air temperature
setpoint
Mixed air temp P-band Xp
MAT XP
Mixed air temp int act time Tn
MAT TN
Path:
INFO
Display
Name
HREC
Mixing damper/HR
Path:
... > COMMIS > TEST
Display
Name
HREC
Mixing damper/HR
Universal Controllers RLU2...
Aggregates
Range / comments
Activation of HR; adjustable values: ---, Y1,
Y2, ...
Adjustable values: ---, X1, X2, ... (only °C,
0.0, 0000, digital)
Adjustable values: ---, X1, X2, ... (only °C,
0.0, 0000)
Adjustable values: ---, X1, X2, ... (only °C,
0.0, 0000)
Adjustable values: ---, X1, X2, ... (inputs
with identifier % only)
---, AO1, AO2, AO3, STP1, STP2, STP3,
SLIN, SBIN, 3P
Range
ERC, DMP
0...100 %
0...100 %
00.00...60.00 m.s 00.00 m.s
-50 °C ... 250 °C 12 °C
0.0 ... 500 K
00.00...60.00 m.s 02.00 m.s
Comments
0...100 %
Positions
---, 0...100 %
Factory setting
ERC
0 %
100 %
3 K, 20 °C
10 K
CE1P3101en
29.08.2008