Siemens Synco 200 Basic Documentation page 162

Universal controllers rlu2
Hide thumbs Also See for Synco 200:
Table of Contents

Advertisement

Aggregates
'd)
(cont
STEP Vx (variable
Configuration
step switch)
• Step 1 to ... (STEP x)
y1 y2
x
IN X
• Modulating output (AO)
STEP V2
Q Q Q Q Q Q
Y
STEP LIN (linear step
Configuration
switch)
• Step 1 to ... (STEP x)
y1 y2
x
IN X
• Modulating output (AO)
STEP LIN
Q Q Q Q Q Q
Y
STEB BIN (binary
Configuration
step switch)
• Step 1 to ... (STEP x)
y1 y2
x
IN X
• Modulating output (AO)
STEP BIN
Q Q Q Q
Y
3P (3-position)
Configuration
• 3-position output (3-POINT)
y1 y2
x
3 POINT
3 P
Q1
Q2
162 / 174
Siemens
Building Technologies
External signal (IN X)
"External preselection" input (IN
X)
"External preselection" input (IN
X)
"External preselection" input (IN
X)
Universal Controllers RLU2...
Appendix
Functions
For controlling a multistage aggregate.
A switch-on and switch-off point can be assigned to each step
according to the load signal from the sequence controller (from up to
2 sequences with maximum selection) The switching points can
overlap and can be inverted (ON < OFF)
External load signal can be applied
Configurable modulating output. Same function as modulating outputs
AO x
Locking time (restart delay) is adjustable (time applies to all steps)
Functions
For controlling a multistage aggregate.
• Linear distribution of the steps over the load signal range according to
the number of outputs assigned
• External load signal can be applied
• Modulating output can be configured, same function as modulating
outputs AO x
• Locking time (restart delay) and startup delay time are adjustable
(time applies to all steps)
Weekly priority changeover of the steps
Functions
For controlling a multistage aggregate.
• Binary distribution of the steps over the load signal range according to
the number of outputs assigned
External load signal can be applied
• Modulating output can be configured, same function as modulating
outputs AO x
Locking time (restart delay) is adjustable (time applies to all steps)
Functions
For controlling a 3-position actuator.
• End stop synchronization
• External load signal can be applied
• Actuator running time adjustable
CE1P3101en
29.08.2008