Siemens Synco 200 Basic Documentation page 37

Universal controllers rlu2
Hide thumbs Also See for Synco 200:
Table of Contents

Advertisement

Availability
Assigning the
identifiers
Notes on units
Further details
Siemens
Building Technologies
7.1.2
Activating the function
Universal Xx inputs are always available. If not required for their functionality, they
can be used for diagnostics purposes.
To activate, assign a LABEL (identifier) to each input used. The identifier also
defines the input's physical unit. The following identifiers are available:
LABEL (identifier)
Explanation
ROOM
Room temperature
OUTS
Outside temperature
SAT
Supply air temperature
Temp
Temperature sensor without dedicated functionality in °C /
°F
%
DC 0...10 V signal, unit %
0.0
Universal input with 1 decimal place,
resolution –99.9...+999.9, increment 0.1
0000
Universal input without decimal place, resolution –
999...+9999, increment 1.
REMx
Absolute setpoint adjuster
Rem setp adjuster relative, in K / °F, range −3...+3 K
REL
FRST
Frost protection
DIG
Digital
There are 2 special features with regard to the assignment of the physical unit:
The unit of room temperature, supply air temperature and outside temperature is
always °C (°F)
Digital inputs do not require units
There is a more detailed description for each specific use of the universal inputs in
the following sections:
Universal inputs used as analog inputs, see 0
Universal inputs used as digital inputs, see 7.3
Universal Controllers RLU2...
Inputs
37 / 174
CE1P3101en
29.08.2008