Siemens Synco 200 Basic Documentation page 104

Universal controllers rlu2
Hide thumbs Also See for Synco 200:
Table of Contents

Advertisement

Configuration
Setting values
104 / 174
Siemens
Building Technologies
9.2.9.4
Settings
Path:
... > COMMIS > CONF > CTLOOP 1
Display
Name
STRATGY Control strategy
Path:
... > PARA > CTLOOP 1
Display
Name
LIM MAX
Gen limiter limit
value high
LIM MIN
Gen limiter limit
value low
LIM DHI
Gen limiter
differential high
LIM DLO
Gen limiter
differential low
LIMCOOL
Reduction min
limitation cooling
LIM XP
Gen limiter P-band
Xp
LIM TN
Gen limiter integr
action time Tn
Universal Controllers RLU2...
Controller (CTLOOP x)
Range / comments
LIM
Range
Input range
limit sensor
Input range
limit sensor
0...500 K
0...500 K
0...10 K
0...500 K
00.00...60.00 m.s
Factory setting
35 °C
16 °C
50 K
50 K
0 K
15 K
02.00 m.s
CE1P3101en
29.08.2008

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents