Summer / Winter Compensation - Siemens Synco 200 Basic Documentation

Universal controllers rlu2
Hide thumbs Also See for Synco 200:
Table of Contents

Advertisement

Controller 1, basic
type A
Function
Diagram
Explanations for the
diagram
Application
Siemens
Building Technologies
9.9

Summer / winter compensation

9.9.1
Activation
Summer / winter compensation is only activated for controller 1, basic type A.
It is always active if an outside temperature signal is available.
9.9.2
Operating principle
This function shifts the room temperature controller's setpoint as a function of the
outside temperature.
This setpoint shift acts on the Comfort and Economy modes according to the
following diagram:
Δw [K]
WIN-D
WIN-END WIN-STT
SUM-STT
w
SETCOOL
SETCOOL
SETHEAT
SETHEAT
Upward shift at low outside temperatures acts on heating and cooling
Downward shift at low outside temperatures acts on heating
Upward shift at high outside temperatures acts on cooling
Downward shift at high outside temperatures acts on heating and cooling
The purpose of summer / winter compensation is as follows:
Summer compensation to compensate for the lighter clothing worn by building
occupants
Winter compensation to compensate for cold surfaces in the room, such as the
windows
Universal Controllers RLU2...
Controller (CTLOOP x)
SUM-D
TA
SUM-END
Legend:
WIN-D
SUM-D
WIN-END
WIN-STT
SUM-STT
SUM-END
OT
w
TA
Δw
Winter comp. delta
Summer comp. delta
Winter comp. end point
Winter comp. starting point
Summer comp. starting point
Summer comp. end point
Outside temperature
Setpoint
Setpoint shift
129 / 174
CE1P3101en
29.08.2008