OT sensor signal
available?
Setting values
130 / 174
Siemens
Building Technologies
9.9.3
Troubleshooting
If there is no outside temperature sensor signal, the controller does not shift the
setpoint.
9.9.4
Settings
Path:
... > PARA > CTLOOP 1
Display
Name
SUM-D
Summer compensation
delta
SUM-END Summer compensation
end
SUM-STT
Summer compensation
start
WIN-STT
Winter compensation start
WIN-END
Winter compensation end
Winter compensation delta −50...+50 K
WIN-D
Universal Controllers RLU2...
Controller (CTLOOP x)
Range
0...+50 K
SUM-STT...50 °C
WIN-STT...SUM-END
WIN-END...SUM-STT
−50 °C...WIN-STT
Factory
setting
0 K
30 °C
20 °C
0 °C
−10 °C
0 K