Siemens Synco 200 Basic Documentation page 83

Universal controllers rlu2
Hide thumbs Also See for Synco 200:
Table of Contents

Advertisement

Configuration
Setting values
Display values
Wiring test
Siemens
Building Technologies
8.5.6
Priorities
The following 2 priorities apply to the step switch:
1 On / Off during the wiring test.
2 Demand-controlled by the sequence controller (preselection in normal
operation) and the external preselection (maximum selection)
8.5.7
Settings
Path:
... > COMMIS > CONF > STEPLIN
Display
Name
STEP 1
Step 1
STEP 2
Step 2
STEP 3
Step 3
STEP 4
Step 4
STEP 5
Step 5
STEP 6
Step 6
AO
Modulating
output
IN X
Preselection
external
Path:
... > PARA > STEPLIN
Display
Name
ON DLY
Startup delay
PRIO CH
Run priority changeover
OFFTIME
Locking time
MIN POS
Positioning signal min
MAX POS Positioning signal max
INVERS
Inversion
Path:
INFO
Display
Name
STEPLIN
Linear step switch
STEP x
Linear step switch, step x
Path:
... > COMMIS > TEST
Display
Name
STEPLIN
Linear step switch
STEP x
Linear step switch, step x
Universal Controllers RLU2...
Aggregates
Range / comments
Activation of step switch and selection of the
number of steps; adjustable values:---, Q1, Q2,
... (free outputs only)
---, Q1, Q2, ... (free outputs only)
---, Q1, Q2, ... (free outputs only)
---, Q1, Q2, ... (free outputs only)
---, Q1, Q2, ... (free outputs only)
---, Q1, Q2, ... (free outputs only)
---, Y1, Y2, ... (free outputs only)
---, X1, X2, ... (inputs with identifier % only)
Range
00.00...10.00 m.s
NO, YES
00.00...10.00 m.s
0...100 %
0...100 %
NO, YES
Comments
0...100 %
ON, OFF
Positions
---, 0...100 %
ON, OFF
Factory setting
00.00
NO
00.00
0 %
100 %
NO
83 / 174
CE1P3101en
29.08.2008