Setting values
Note
Display values
Wiring test
78 / 174
Siemens
Building Technologies
Path:
... > PARA > STEP V1
... > PARA > STEP V2
Display
Name
S1-ON
[Step 1] ON
S1-OFF
[Step 1] OFF
S2-ON
[Step 2] ON
S2-OFF
[Step 2] OFF
S3-ON
[Step 3] ON
S3-OFF
[Step 3] OFF
S4-ON
[Step 4] ON
S4-OFF
[Step 4] OFF
S5-ON
[Step 5] ON
S5-OFF
[Step 5] OFF
S6-ON
[Step 6] ON
S6-OFF
[Step 6] OFF
OFFTIME
Locking time
MIN POS
Positioning signal min
MAX POS
Positioning signal max
INVERS
Inversion
STEP V1 has a maximum of 2 steps.
Therefore, the setting values for S3-ON to S6-OFF are not shown.
Path:
INFO
Display
Name
STEP V1
Variable step switch 1
STEP x
Variable step switch 1, step x
STEP V2
Variable step switch 2
STEP x
Variable step switch 2, step x
Path:
... > COMMIS > TEST
Display
Name
STEP V1
Variable step switch 1
STEP x
Variable step switch 1, step x
STEP V2
Variable step switch 2
STEP x
Variable step switch 2, step x
Universal Controllers RLU2...
Aggregates
Range
Factory setting
0...100 %
17 %
0...100 %
1 %
0...100 %
33 %
0...100 %
17 %
0...100 %
50 %
0...100 %
33 %
0...100 %
67 %
0...100 %
50 %
0...100 %
83 %
0...100 %
67 %
0...100 %
100 %
0...100 %
83 %
00.00...10.00 m.s
00.00 m.s
0...100 %
0 %
0...100 %
100 %
NO, YES
NO
Comments
0...100 %
ON, OFF
0...100 %
ON, OFF
Positions
---, 0...100 %
ON, OFF
---, 0...100 %
ON, OFF
CE1P3101en