Outputs Y and P
Activation rules
Available load outputs
Load output rules
Siemens
Building Technologies
9.5.3
Assigning outputs to sequences
Each sequence has 2 outputs:
1 load output SEQx Y
1 pump output SEQx P
You can occupy both.
9.5.4
Activating the sequences
To activate a sequence, assign either a load output or a pump output to it.
When neither a load output nor a pump output is assigned to a sequence, this
sequence and all subsequent sequences (within heating or cooling) will be
deactivated.
9.5.5
Load outputs
The following load outputs are available for the sequence controllers:
Modulating output
Heat recovery
Variable step switch
Linear step switch
Binary step switch
3-position output (with RLU222 and RLU202 only)
Only one load output can be assigned to each sequence.
However, each load output can be commanded by up to 2 sequences (from the
same or different control loops).
Universal Controllers RLU2...
Controller (CTLOOP x)
115 / 174
CE1P3101en
29.08.2008