Wiring test

When the peripheral equipment is connected, you can perform a wiring test in the
TEST (wiring test) menu. We recommend testing after configuration and settings
are complete. The test provides the following functions:
Display of reading values for inputs
Switching of aggregates connected to the outputs, such as pumps
Preselection of a 0...100% signal for step switches, where the relays are
switched
The application is deactivated during the wiring test. The outputs are in a defined
OFF state, and safety-related functions (e.g. frost protection) are deactivated!
The wiring test provides checks for the following errors at the inputs and outputs:
Connection error (mixed up wires)
Position error (mixed up sensors or actuating devices)
Discrepancies between connection method and controller configuration (LG-
Ni1000 in place of active DC 0...10 V)
Universal Controllers RLU2...
Commissioning
CE1P3101en