Information List - Siemens SIPROTEC 7SD80 Manual

The digital overcurrent protection
Hide thumbs Also See for SIPROTEC 7SD80:
Table of Contents

Advertisement

Functions
2.14 Monitoring Functions
Addr.
Parameter
2914A
FFM Idiff (3ph)
2915
V-Supervision
2916A
T V-Supervision
2931
BROKEN WIRE
FAST Σ i SUPERV
2933
ΔI min
2935A

2.14.1.7 Information List

No.
Information
161
Fail I Superv.
163
Fail I balance
164
Fail V Superv.
167
Fail V balance
168
Fail V absent
169
VT FuseFail>10s
170
VT FuseFail
171
Fail Ph. Seq.
196
Fuse Fail M.OFF
197
MeasSup OFF
Failure Σi
289
290
Broken Iwire L1
291
Broken Iwire L2
292
Broken Iwire L3
295
Broken wire OFF
Σi superv. OFF
296
297
ext.Brk.Wire ØA
298
ext.Brk.Wire ØB
299
ext.Brk.Wire ØC
3270
>RESET BW
3271
Broken Iwire a
3272
Broken Iwire b
3273
Broken Iwire c
178
C
Setting Options
1A
0.05 .. 1.00 A
5A
0.25 .. 5.00 A
w/ CURR.SUP
w/ I> & 52a
OFF
0.00 .. 30.00 sec
ON
OFF
Alarm only
ON
OFF
1A
0.05 .. 1.00 A
5A
0.25 .. 5.00 A
Type of In-
formation
OUT
Failure: General Current Supervision
OUT
Failure: Current Balance
OUT
Failure: General Voltage Supervision
OUT
Failure: Voltage Balance
OUT
Failure: Voltage absent
OUT
VT Fuse Failure (alarm >10s)
OUT
VT Fuse Failure (alarm instantaneous)
OUT
Failure: Phase Sequence
OUT
Fuse Fail Monitor is switched OFF
OUT
Measurement Supervision is switched OFF
OUT
Alarm: Current summation supervision
OUT
Alarm: Broken current-wire detected L1
OUT
Alarm: Broken current-wire detected L2
OUT
Alarm: Broken current-wire detected L3
OUT
Broken wire supervision is switched OFF
OUT
Current summation superv is switched OFF
OUT
Broken current-wire at other end ØA
OUT
Broken current-wire at other end ØB
OUT
Broken current-wire at other end ØC
SP
>RESET broken wire monitoring
IntSP
Alarm: Broken current-wire detected A
IntSP
Alarm: Broken current-wire detected B
IntSP
Alarm: Broken current-wire detected C
Default Setting
0.10 A
Differential Current
Threshold (3phase)
0.50 A
w/ CURR.SUP
Voltage Failure Supervi-
sion
3.00 sec
Delay Voltage Failure Su-
pervision
OFF
Fast broken current-wire
supervision
ON
State of fast current sum-
mation supervis
0.10 A
Min. current diff. for wire
break det.
0.50 A
Comments
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011