Functions
2.8 Undervoltage and Overvoltage Protection 27/59 (Optional)
Addr.
Parameter
3773
27-1-V1 DELAY
3774
27-2-V1 PICKUP
3775
27-2-V1 DELAY
3778
CURR.SUP. 27-V1
3779A
27-V1 RESET
2.8.5

Information List

No.
Information
234.2100 27, 59 blk
10201
>59-Vphg BLOCK
10202
>59-Vphph BLOCK
10203
>59-3V0 BLOCK
10204
>59-V1 BLOCK
10205
>59-V2 BLOCK
10206
>27-Vphg BLOCK
10207
>27-Vphph BLOCK
10208
>27-V1 BLOCK
10215
59-Vphg OFF
10216
59-Vphg BLK
10217
59-Vphph OFF
10218
59-Vphph BLK
10219
59-3V0 OFF
10220
59-3V0 BLK
10221
59-V1 OFF
10222
59-V1 BLK
10223
59-V2 OFF
10224
59-V2 BLK
10225
27-Vphg OFF
10226
27-Vphg BLK
10227
27-Vphph OFF
10228
27-Vphph BLK
10229
27-V1 OFF
10230
27-V1 BLK
10231
27/59 ACTIVE
10240
59-1-Vpg Pickup
10241
59-2-Vpg Pickup
10242
59-Vpg PU A
10243
59-Vpg PU B
10244
59-Vpg PU C
10245
59-1-VpgTimeOut
10246
59-2-VpgTimeOut
130
Setting Options
0.00 .. 100.00 sec; ∞
1.0 .. 100.0 V; 0
0.00 .. 100.00 sec; ∞
ON
OFF
1.01 .. 1.20
Type of In-
formation
IntSP
27, 59 blocked via operation
SP
>BLOCK 59-Vphg Overvolt. (phase-ground)
SP
>BLOCK 59-Vphph Overvolt (phase-phase)
SP
>BLOCK 59-3V0 Overvolt. (zero sequence)
SP
>BLOCK 59-V1 Overvolt. (positive seq.)
SP
>BLOCK 59-V2 Overvolt. (negative seq.)
SP
>BLOCK 27-Vphg Undervolt. (phase-ground)
SP
>BLOCK 27-Vphph Undervolt (phase-phase)
SP
>BLOCK 27-V1 Undervolt (positive seq.)
OUT
59-Vphg Overvolt. is switched OFF
OUT
59-Vphg Overvolt. is BLOCKED
OUT
59-Vphph Overvolt. is switched OFF
OUT
59-Vphph Overvolt. is BLOCKED
OUT
59-3V0 Overvolt. is switched OFF
OUT
59-3V0 Overvolt. is BLOCKED
OUT
59-V1 Overvolt. is switched OFF
OUT
59-V1 Overvolt. is BLOCKED
OUT
59-V2 Overvolt. is switched OFF
OUT
59-V2 Overvolt. is BLOCKED
OUT
27-Vphg Undervolt. is switched OFF
OUT
27-Vphg Undervolt. is BLOCKED
OUT
27-Vphph Undervolt. is switched OFF
OUT
27-Vphph Undervolt. is BLOCKED
OUT
27-V1 Undervolt. is switched OFF
OUT
27-V1 Undervolt. is BLOCKED
OUT
27/59 Voltage protection is ACTIVE
OUT
59-1-Vphg Pickup
OUT
59-2-Vphg Pickup
OUT
59-Vphg Pickup A
OUT
59-Vphg Pickup B
OUT
59-Vphg Pickup C
OUT
59-1-Vphg TimeOut
OUT
59-2-Vphg TimeOut
Default Setting
2.00 sec
27-1 Time Delay
10.0 V
27-2 Pickup Undervoltage (pos.
seq.)
1.00 sec
27-2 Time Delay
ON
Current supervision (V1)
1.05
Reset ratio
Comments