Siemens SIPROTEC 7SD80 Manual page 370

The digital overcurrent protection
Hide thumbs Also See for SIPROTEC 7SD80:
Table of Contents

Advertisement

Appendix
A.8 Settings
Addr.
Parameter
4205
I ALARM
4206
CALC. METHOD
4501
PDI FO
4502
PDI FO TER
4503
PDI FO level
4510
TD-DATA DISTURB
4512
Td ResetRemote
4601
PDI Cu
4602
PDI Cu TER
4603
PDI Cu mode
4604
PDI Cu MAX ATT
4605
PDI Cu S/N
4701
ID OF MASTER
4702
ID OF SLAVE
4710
LOCAL RELAY
370
Function
C
Setting Options
49 Th.Overload
1A
0.10 .. 4.00 A
5A
0.50 .. 20.00 A
Θ max
49 Th.Overload
Average Θ
Θ from Imax
Prot.Interface
ON
OFF
Prot.Interface
0.5 .. 20.0 %
Prot.Interface
-30 .. -10 dBm
Prot.Interface
0.05 .. 2.00 sec
0.00 .. 300.00 sec; ∞
Prot.Interface
Prot.Interface
ON
OFF
Prot.Interface
0.5 .. 20.0 %
Prot.Interface
01
02
03
04
05
06
Prot.Interface
0 .. 46 dB
Prot.Interface
6 .. 30 dB
Diff.-Topo
1 .. 65534
Diff.-Topo
1 .. 65534
Diff.-Topo
Master
Slave
Default Setting
1.00 A
Current Overload Alarm Setpoint
5.00 A
Θ max
Method of Acquiring Tempera-
ture
ON
Protection Data Interface fiber
optic
1.0 %
PDI FO max. telegram error rate
-28 dBm
PDI FO min. receive level
0.10 sec
Time delay for data disturbance
alarm
0.00 sec
Remote signal RESET DELAY
for comm.fail
ON
Protection Data Interface copper
1.0 %
PDI Cu max. telegram error rate
01
PDI Cu operation mode
46 dB
PDI Cu maximum attenuation
6 dB
PDI Cu min signal to noise ratio
1
Identification number of Master
2
Identification number of Slave
Master
Local relay is
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011