Functions
2.5 Inrush Restraint
2.5.3

Settings

Addr.
Parameter
2301
INRUSH REST.
2302
2nd HARMONIC
2303
CROSS BLOCK
2305
MAX INRUSH PEAK
2310
CROSSB 2HM
2.5.4

Information List

No.
Information
3102
2nd Harmonic A
3103
2nd Harmonic B
3104
2nd Harmonic C
100
Setting Options
OFF
ON
10 .. 45 %
NO
YES
1.1 .. 25.0 A
0.00 .. 60.00 sec; ∞
Type of In-
formation
OUT
Tolerance invalid in phase A
OUT
Tolerance invalid in phase B
OUT
Tolerance invalid in phase C
Default Setting
OFF
Inrush Restraint
15 %
2nd. harmonic in % of fundamen-
tal
NO
Cross Block
15.0 A
Maximum inrush-peak value
0.00 sec
Time for Crossblock with 2nd har-
monic
Comments
E50417-G1140-C474-A1, Release date 09.2011