The digital overcurrent protection
Hide thumbs Also See for SIPROTEC 7SD80:
Table of Contents

Advertisement

Functions
2.8 Undervoltage and Overvoltage Protection 27/59 (Optional)
Overvoltage Positive Sequence System V
The device calculates the positive sequence system according to its defining equation
1
V
=
/
·(V
+ a·V
1
3
A
j120°
where a = e
.
The resulting positive sequence voltage is fed to the two threshold elements 59-1-V1 PICKUP (address
3732) and 59-2-V1 PICKUP (address 3734) (see Figure 2-47). Combined with the associated time delays
59-1-V1 DELAY (address 3733) and 59-2-V1 DELAY (address 3735) these elements form a two-element
overvoltage protection for the positive sequence system. Here too, the dropout ratio can be set.
The overvoltage protection for the positive sequence system can also be blocked via a binary input „>59-V1
BLOCK".
Figure 2-47
Logic diagram of the overvoltage protection for the positive sequence voltage system