Undervoltage Phase-to-Phase
Basically, the same considerations apply as for the phase undervoltage elements. These elements may
replace the phase voltage elements or be used additionally. Accordingly set address 3761 27-Vph-ph Mode
to ON, OFF, Alarm Only or V<Alarm V<<Trip.
As phase–to–phase voltages are monitored, the phase–to–phase values are used for the settings 27-1-Vpp
PICKUP (address 3762) and 27-2-Vpp PICKUP (address 3764).
The corresponding times delay are 27-1-Vpp DELAY (address 3763) and 27-2-Vpp DELAY (address
3765).
The dropout to pickup ratio 27-Vph-ph RESET can be set in address 3769. This parameter can only be set
in DIGSI at Display Additional Settings.
If the voltage transformers are located on the line side, the measuring voltages will be absent when the line is
disconnected. To avoid that the undervoltage levels in these cases are or remain picked up, the current criterion
CURR.SUP 27-Vpp (address 3768) is switched ON. With bus-sided voltage transformers it can be switched
OFF. However, if the busbar is dead, the undervoltage protection will pick up and expire and then remain picked
up. It must therefore be ensured that the protection is blocked by a binary input.
Undervoltage Positive Sequence System V
The positive sequence undervoltage elements can be used instead of or in addition to previously mentioned
undervoltage elements. Accordingly set address 3771 27-V1 Mode to ON, OFF, Alarm Only or V<Alarm
V<<Trip.
Basically, the same considerations apply as for the other undervoltage elements. Especially in case of stability
problems, the positive sequence system is advantageous, since the positive sequence system is relevant for
the limit of the stable energy transmission.
To achieve the two-element condition, the 27-1-V1 PICKUP element (address 3772) is combined with a
greater time delay 27-1-V1 DELAY (address 3773), and the 27-2-V1 PICKUP element (address 3774) with
a shorter time delay 27-2-V1 DELAY (address 3775).
Note that the positive sequence system is established according to its defining equation
1
V
=
/
·|V
+ a·V
1
3
A
The dropout to pickup ratio 27-V1 RESET can be set in address 3779. This parameter can only be set in DIGSI
at Display Additional Settings.
If the voltage transformers are located on the line side, the measuring voltages will be missing when the line is
disconnected. To avoid that the undervoltage levels in these cases are or remain picked up, the current criterion
CURR.SUP. 27-V1 (address 3778) is switched ON. With bus-sided voltage transformers it can be switched
OFF. However, if the busbar is dead, the undervoltage protection will pick up and expire and then remain in a
picked-up state. It must therefore be ensured in such cases that the protection is blocked by a binary input.
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
1
2
+ a
·V
|. For symmetrical voltages this is equivalent to a phase-ground voltage.
B
C
2.8 Undervoltage and Overvoltage Protection 27/59 (Optional)
Functions
127