4.13
Automatic Reclosing (Optional)
Automatic Reclosures
Number of reclosures
Type (depending on order variant)
Control
Action times
Initiation possible without pickup and action time
Dead times prior to reclosure
separately for all types and all cycles
Dead times after evolving fault recognition
Blocking time after reclosure
Blocking time after dynamic blocking
Blocking time after manual closing
Start signal monitoring time
Circuit breaker monitoring time
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
max. 2
3-pole
with pickup or trip command
0.01 s to 300.00 s; ∞
0.01 s to 1800.00 s; ∞
0.01 s to 1800.00 s
0.50 s to 300.00 s
0.5 s
0.50 s to 300.00 s; 0
0.01 s to 300.00 s
0.01 s to 300.00 s
Technical Data
4.13 Automatic Reclosing (Optional)
Increments 0.01 s
Increments 0.01 s
Increments 0.01 s
Increments 0.01 s
Increments 0.01 s
Increments 0.01 s
Increments 0.01 s
317