Siemens SIPROTEC 7SD80 Manual page 369

The digital overcurrent protection
Hide thumbs Also See for SIPROTEC 7SD80:
Table of Contents

Advertisement

Addr.
Parameter
3755
27-2-Vph DELAY
3758
CURR.SUP 27-Vph
3759A
27-Vph RESET
3761
27-Vph-ph Mode
3762
27-1-Vpp PICKUP
3763
27-1-Vpp DELAY
3764
27-2-Vpp PICKUP
3765
27-2-Vpp DELAY
3768
CURR.SUP 27-Vpp
3769A
27-Vph-ph RESET
3771
27-V1 Mode
3772
27-1-V1 PICKUP
3773
27-1-V1 DELAY
3774
27-2-V1 PICKUP
3775
27-2-V1 DELAY
3778
CURR.SUP. 27-V1
3779A
27-V1 RESET
3901
FCT 50BF Break.
3902
50BF PICKUP
3905
50BF-1 Delay 3p
3906
50BF-2 Delay
3907
T3-BkrDefective
3908
Trip BkrDefect.
3909
Chk BRK CONTACT
3912
50NBF PICKUP
3913
T2StartCriteria
3921
End Flt. elem.
3922
EndFault Delay
4001
FCT 74TC
4002
No. of BI
4003
Alarm Delay
4201
FCT 49
4202
49 K-FACTOR
4203
TIME CONSTANT
49 Θ ALARM
4204
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
Function
C
Setting Options
0.00 .. 100.00 sec; ∞
27/59 O/U Volt.
27/59 O/U Volt.
ON
OFF
27/59 O/U Volt.
1.01 .. 1.20
27/59 O/U Volt.
OFF
Alarm Only
ON
V<Alarm V<<Trip
27/59 O/U Volt.
1.0 .. 175.0 V; 0
0.00 .. 100.00 sec; ∞
27/59 O/U Volt.
27/59 O/U Volt.
1.0 .. 175.0 V; 0
0.00 .. 100.00 sec; ∞
27/59 O/U Volt.
27/59 O/U Volt.
ON
OFF
27/59 O/U Volt.
1.01 .. 1.20
27/59 O/U Volt.
OFF
Alarm Only
ON
V<Alarm V<<Trip
27/59 O/U Volt.
1.0 .. 100.0 V; 0
0.00 .. 100.00 sec; ∞
27/59 O/U Volt.
27/59 O/U Volt.
1.0 .. 100.0 V; 0
0.00 .. 100.00 sec; ∞
27/59 O/U Volt.
27/59 O/U Volt.
ON
OFF
27/59 O/U Volt.
1.01 .. 1.20
50BF BkrFailure
ON
OFF
50BF BkrFailure
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
0.00 .. 30.00 sec; ∞
50BF BkrFailure
0.00 .. 30.00 sec; ∞
50BF BkrFailure
0.00 .. 30.00 sec; ∞
50BF BkrFailure
50BF BkrFailure
NO
with Local trip
with Bus trip
w/Local&Bustrip
50BF BkrFailure
NO
YES
50BF BkrFailure
1A
0.05 .. 20.00 A
5A
0.25 .. 100.00 A
50BF BkrFailure
With exp. of T1
Parallel withT1
50BF BkrFailure
ON
OFF
0.00 .. 30.00 sec; ∞
50BF BkrFailure
74TC TripCirc.
ON
OFF
74TC TripCirc.
1 .. 2
74TC TripCirc.
1 .. 30 sec
49 Th.Overload
OFF
ON
Alarm Only
49 Th.Overload
0.10 .. 4.00
49 Th.Overload
1.0 .. 999.9 min
49 Th.Overload
50 .. 100 %
Default Setting
1.00 sec
27-2 Time Delay
ON
Current supervision (Vph-g)
1.05
Reset ratio
OFF
Operating mode Vph-ph under-
voltage prot.
50.0 V
27-1 Pickup Undervoltage
(phase-phase)
2.00 sec
27-1 Time Delay
17.0 V
27-2 Pickup Undervoltage
(phase-phase)
1.00 sec
27-2 Time Delay
ON
Current supervision (Vph-ph)
1.05
Reset ratio
OFF
Operating mode V1 Undervolt-
age prot.
30.0 V
27-1 Pickup Undervoltage (pos.
seq.)
2.00 sec
27-1 Time Delay
10.0 V
27-2 Pickup Undervoltage (pos.
seq.)
1.00 sec
27-2 Time Delay
ON
Current supervision (V1)
1.05
Reset ratio
ON
50BF Breaker Failure Protection
0.10 A
50BF Pickup current threshold
0.50 A
0.00 sec
Delay after 3pole start for local
trip
0.15 sec
Delay of 2nd element for busbar
trip
0.00 sec
Delay for start with defective bkr.
NO
Trip output selection with defec-
tive bkr
YES
Check Breaker contacts
0.10 A
50NBF Pickup neutral current
threshold
0.50 A
Parallel withT1
T2 Start Criteria
OFF
End fault element
2.00 sec
Trip delay of end fault element
OFF
74TC TRIP Circuit Supervision
2
Number of Binary Inputs per trip
circuit
2 sec
Delay Time for alarm
OFF
49 Thermal overload protection
1.10
49 K-Factor
100.0 min
Time Constant
90 %
49 Thermal Alarm Stage
Appendix
A.8 Settings
Comments