Appendix
A.8 Settings
Addr.
Parameter
2801
DMD Interval
2802
DMD Sync.Time
2811
MinMax cycRESET
2812
MiMa RESET TIME
2813
MiMa RESETCYCLE
2814
MinMaxRES.START
2901
MEASURE. SUPERV
2902A
BALANCE V-LIMIT
2903A
BAL. FACTOR V
2904A
BALANCE I LIMIT
2905A
BAL. FACTOR I
Σ I THRESHOLD
2906A
Σ I FACTOR
2907A
2908A
T BAL. V LIMIT
2909A
T BAL. I LIMIT
2910
FUSE FAIL MON.
2911A
FFM V>(min)
2912A
FFM I< (max)
2913A
FFM V<max (3ph)
2914A
FFM Idiff (3ph)
2915
V-Supervision
2916A
T V-Supervision
2931
BROKEN WIRE
FAST Σ i SUPERV
2933
ΔI min
2935A
3401
FCT 79
3402
52? 1.TRIP
3403
T-RECLAIM
3404
BLOCK MC Dur.
3406
EV. FLT. RECOG.
366
Function
C
Setting Options
Demand meter
15 Min., 1 Sub
15 Min., 3 Subs
15 Min.,15 Subs
30 Min., 1 Sub
60 Min., 1 Sub
Demand meter
On The Hour
15 After Hour
30 After Hour
45 After Hour
Min/Max meter
NO
YES
Min/Max meter
0 .. 1439 min
Min/Max meter
1 .. 365 Days
Min/Max meter
1 .. 365 Days
Measurem.Superv
ON
OFF
Measurem.Superv
10 .. 100 V
Measurem.Superv
0.58 .. 0.95
Measurem.Superv
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
Measurem.Superv
0.10 .. 0.95
Measurem.Superv
1A
0.10 .. 2.00 A
5A
0.50 .. 10.00 A
Measurem.Superv
0.00 .. 0.95
Measurem.Superv
5 .. 100 sec
Measurem.Superv
5 .. 100 sec
Measurem.Superv
ON
OFF
Measurem.Superv
10 .. 100 V
Measurem.Superv
1A
0.10 .. 1.00 A
5A
0.50 .. 5.00 A
Measurem.Superv
2 .. 100 V
Measurem.Superv
1A
0.05 .. 1.00 A
5A
0.25 .. 5.00 A
Measurem.Superv
w/ CURR.SUP
w/ I> & 52a
OFF
Measurem.Superv
0.00 .. 30.00 sec
Measurem.Superv
ON
OFF
Alarm only
Measurem.Superv
ON
OFF
Measurem.Superv
1A
0.05 .. 1.00 A
5A
0.25 .. 5.00 A
79 Auto Recl.
OFF
ON
79 Auto Recl.
YES
NO
79 Auto Recl.
0.50 .. 300.00 sec
79 Auto Recl.
0.50 .. 300.00 sec; 0
79 Auto Recl.
with PICKUP
with TRIP
Default Setting
60 Min., 1 Sub
Demand Calculation Intervals
On The Hour
Demand Synchronization Time
YES
Automatic Cyclic Reset Function
0 min
MinMax Reset Timer
7 Days
MinMax Reset Cycle Period
1 Days
MinMax Start Reset Cycle in
ON
Measurement Supervision
50 V
Voltage Threshold for Balance
Monitoring
0.75
Balance Factor for Voltage
Monitor
0.50 A
Current Threshold for Balance
Monitoring
2.50 A
0.50
Balance Factor for Current
Monitor
0.25 A
Summated Current Monitoring
Threshold
1.25 A
0.50
Summated Current Monitoring
Factor
5 sec
T Balance Factor for Voltage
Monitor
5 sec
T Current Balance Monitor
ON
Fuse Failure Monitor
30 V
Minimum Voltage Threshold V>
0.10 A
Maximum Current Threshold I<
0.50 A
5 V
Maximum Voltage Threshold V<
(3phase)
0.10 A
Differential Current Threshold
(3phase)
0.50 A
w/ CURR.SUP
Voltage Failure Supervision
3.00 sec
Delay Voltage Failure Supervi-
sion
OFF
Fast broken current-wire supervi-
sion
ON
State of fast current summation
supervis
0.10 A
Min. current diff. for wire break
det.
0.50 A
ON
79 Auto-Reclose Function
NO
52-ready interrogation at 1st trip
3.00 sec
Reclaim time after successful AR
cycle
1.00 sec
AR blocking duration after
manual close
with TRIP
Evolving fault recognition
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011