Technical Data
4.1 General Device Data
IEC 60870-5-103
redundant
RS485
Profibus RS485 (DP)
Profibus FO (DP)
DNP3.0 /MODBUS RS485
DNP3.0 /MODBUS FO
286
Isolated interface for data transfer to a control center
Connection
Test voltage
Transmission speed
Bridgeable distance
Connection
Test voltage
Transmission speed
Bridgeable distance
FO connector type
Connection
Transmission speed
Recommended:
Optical wavelength
Laser Class 1 according to EN
60825-1/-2
Permissible optical signal at-
tenuation
Bridgeable distance
Connection
Test voltage
Transmission speed
Bridgeable distance
FO connector type
Connection
Transmission speed
Optical wavelength
Laser Class 1 according to EN
60825-1/-2
Permissible optical signal at-
tenuation
Bridgeable distance
Back case bottom, mounting location "B",
RJ45 socket
500 V; 50 Hz
min. 2 400 Bd, max. 57 600 Bd;
factory setting 19 200 Bd
Max. 0.62 miles
Back housing bottom, mounting location "B",
9-pin D-sub socket via straight Profibus con-
nector (6KG1500-0EA02 )
500 V; 50 Hz
Up to 1.5 MBd
1 000 m (0.62 miles) at ≤ 93.75 kBd
546.81 yd at ≤ 187.5 kBd
218.72 yd at ≤ 1.5 MBd
ST connector
Double ring
Back case bottom, mounting location "B"
Up to 1.5 MBd
> 500 kBd with normal casing
λ = 820 nm
When using glass fiber 50/125 μm or glass
fiber 62.5/125 µm
max. 8 dB, with glass fiber 62.5/125 µm
Max. 0.93 miles
Back case bottom, mounting location "B", 9-
pin DSUB socket
500 V; 50 Hz
Up to 19.200 Baud
Max. 0.62 miles
ST connector transmitter/receiver
Back case bottom, rear mounting location
"B"
Up to 19.200 Baud
λ = 820 nm
When using glass fiber 50/125 μm or glass
fiber 62.5/125 µm
max. 8 dB, with glass fiber 62.5/125 µm
Max. 0.93 miles
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011