Siemens SIPROTEC 7SD80 Manual page 175

The digital overcurrent protection
Hide thumbs Also See for SIPROTEC 7SD80:
Table of Contents

Advertisement

Table 2-4
Summary of the Device's Fault Responses
Monitoring
Possible causes
Auxiliary voltage
External (aux. voltage) Inter-
failure
nal (converter)
Measured-value ac-
Internal (converter or refer-
quisition
ence voltage)
Buffer battery
Internal (Buffer battery)
Hardware watchdog Internal (processor failure)
Software watchdog Internal (program sequence) Restart attempt
Working memory
Internal (RAM)
ROM
Program memory
Internal (EPROM)
RAM
Settings memory
Internal (Flash-EPROM or
RAM)
Sampling frequency Internal (clock generator)
Adjustment values
Internal (EEPROM or RAM) Indication:
Modules
Module does not comply
with order number (MLFB)
Current sum
Internal (measured value
acquisition)
Current symmetry
External (power system or
current transformer)
Broken wire
External (power system or
current transformer)
Voltage symmetry
External (power system or
voltage transformer)
Voltage phase se-
External (power system or
quence
connection)
Voltage failure,
External (power system or
3-phase „Fuse
connection)
Failure Monitor"
Voltage loss,
External (voltage transform-
„Fuse failure moni-
ers)
tor"
Voltage failure,
External (power system or
3-phase
connection)
Trip circuit
External (trip circuit or
supervision
control voltage)
1)
Following three unsuccessful restarting attempts, the device is put out of operation
2)
DOK = „Device OK" = NC contact of the readiness relay = life contact
SIPROTEC, 7SD80, Manual
E50417-G1140-C474-A1, Release date 09.2011
Fault response
Device out of operation
All LEDs dark
Protection out of opera-
ERROR „LED"
tion, alarm
„Error A/D-conv." (181)
Indication
„Fail Battery" (177)
Device out of operation
ERROR „LED"
1)
ERROR „LED"
1)
Restart attempt
, Restart
LED flashes
abort
Device out of operation
1)
Restart attempt
ERROR „LED"
1)
Restart attempt
ERROR „LED"
1)
Restart attempt
ERROR „LED"
„Alarm adjustm." (193)
Using default values
Indications:
„Error Board 1...5" (183
Protection out of operation
... 187)
and if applicable
„Error A/D-conv.". (181)
„Failure Σi" (289)
Indication
Total blocking of the differ-
ential protection
Indication
„Fail I balance" (163)
Indication
„Broken Iwire L1" (290),
Phase-selective blocking
„Broken Iwire L2" (291),
of the differential protec-
„Broken Iwire L3" (292)
tion
Indication
„Fail V balance" (167)
Indication
„Fail Ph. Seq." (171)
Indication
„VT FuseFail>10s"
Undervoltage protection
(169),
blocked,
„VT FuseFail" (170)
Frequency protection
blocked
Indication
„VT FuseFail>10s"
Undervoltage protection
(169),
blocked,
„VT FuseFail" (170)
Indication
„Fail V absent" (168)
Undervoltage protection
blocked,
Indication
„74TC Trip cir." (6865)
2.14 Monitoring Functions
Indication (no.)
Output
2)
DOK
2)
DOK
As routed
2)
DOK
2)
DOK
2)
DOK
2)
DOK
2)
DOK
2)
DOK
As routed
2)
DOK
As routed
As routed
As routed
As routed
As routed
As routed
As routed
As routed
As routed
Functions
drops out
drops out
drops out
drops out
drops out
drops out
drops out
drops out
drops out
175