Section 4: System Configuration; Entry/Exit Delay - Response CENTURION SCOUT Owner's Manual

Table of Contents

Advertisement

SYSTEM CONFIGURATION
The Centurion SCOUT Portable Alert System is DISARMED when a user is configuring
the system.
DO NOT configure the system when sensors must be monitored.
If the system is DISARMED, alarms WILL NOT BE PROCESSED or LOGGED.
Sensors activated while the unit is disarmed will not transmit alarms via the radio system
or other communication interface option.

ENTRY/EXIT DELAY

Press the ENTRY/EXIT DELAY key and follow verbal prompts to desired setting. From
Entry/Exit Delay OFF status (LEDs not lit), press key one time to only turn on Entry Delay;
press key two times to turn on Exit Delay; press key three times to turn on Entry Delay and Exit
Delay; press key four times to turn off Entry Delay and Exit Delay.
Entry Delay
Entry Delay is ON when ENTRY LED is lit. Default Entry Delay is 30 seconds. Selecting Entry
Delay will transmit alert message in 30 seconds unless SCOUT is disarmed during the Entry
Delay period. Entry Delay time is configurable with provided Console software (see Console
Configurations – Section 5).
Exit Delay
Exit Delay is ON when EXIT LED is lit. Default Exit Delay is 90 seconds. Selecting Exit Delay
will arm the SCOUT 90 seconds after pressing the SYSTEM ARMED/DISARMED key
allowing user to exit premises before system arms. During the 90 second delay, SYSTEM
ARMED/DISARMED LED will blink. After 90 second delay system will arm and SYSTEM
ARMED/DISARMED LED will be lit. Exit Delay time is configurable with provided Console
software (see Console Configurations – Section 5).
www.response-technologies.com
- 7 -
Section 4
System Configuration
©Response Technologies, Ltd.
Revised: January 9, 2015

Advertisement

Table of Contents
loading

Table of Contents