Plant Operating Mode - Siemens Synco living Operating Instructions Manual

Hide thumbs Also See for Synco living:
Table of Contents

Advertisement

Plant operating mode

The individual rooms can be configured merely for heating/cooling operation,
or for automatic changeover between the two operating modes.
Main menu > Rooms > Room X > Room operating mode
> Plant optg mode:
Auto
The plant operating mode is changed over automatically based
on room temperature and mixed outside temperature.
Heating
The plant is in heating mode.
Cooling
The plant is in cooling mode.
Plants with rooms featuring controllable air conditioners can heat or
cool the rooms independent of each other.
The individual air conditioners are controlled via infrared interface and
a Zennio module (KNX S-mode).
Room number
Room name
Factory setting
Setting
Room number
Room name
Factory setting
Setting
Auto = Automatic changeover between heating and cooling
Heat. = Heating
Cool. = Cooling
H/C-changeover in Auto plant operating mode
In case of automatic changeover, the central apartment unit checks first the
room temperature and compares it to the average value from the heating
Comfort setpoint and the cooling Comfort setpoint ((H Cw + K Cw) / 2).
If the room temperature is at least 0.5 °C below the average value, heating
mode is released
If the room temperature is at least 0.5 °C above the average value, cooling
mode is released
H
Siemens
Building Technologies
1
2
Auto
Auto
Auto
Auto
Heat.
Heat.
Cool.
Cool.
7
8
Auto
Auto
Auto
Auto
Heat.
Heat.
Cool.
Cool.
Synco™ living Operating instructions
Central apartment unit QAX910
3
4
Auto
Auto
Auto
Auto
Heat.
Heat.
Cool.
Cool.
9
10
Auto
Auto
Auto
Auto
Heat.
Heat.
Cool.
Cool.
H
Heating mode
K
Cooling mode
H Cw
Heating Comfort setpoint
K Cw
Cooling Comfort setpoint
TR
Room temperature
5
6
Auto
Auto
Auto
Auto
Heat.
Heat.
Cool.
Cool.
11
12
Auto
Auto
Auto
Auto
Heat.
Heat.
Cool.
Cool.
33 / 100
CE1B2707en
23.08.2008

Hide quick links: