7.9.4
Ethernet network settings (Installer menu)
To connect the unit to the local Ethernet network for operation in Master/
Slave mode, software Backup/Rotation or use the webserver, set the
DHCP, IP, subnet mask, gateway and DNS parameters.
Important: these values must be provided by the local network
administrator.
Index
Description
Parameter
Eh04
Ethernet net-
Set the unit's IP address for the Ethernet connection. Set
work settings
DHCP, subnet mask, gateway, DNS.
Defaults:
DHCP: Off
IP: 192.168.0.1 (unit's IP address)
Mask: 255.255.255.0 (subnet mask)
GW: 192.168.0.1 (gateway)
DNS: 0.0.0.0
Update?: NO
The following values are set by default on each unit:
DHCP: Off
unit's IP address: 192.168.0.1
subnet mask: 255.255.255.0
gateway: 192.168.0.1
DNS: 0.0.0.0
After having modifi ed the parameters, set the "Update?" parameter to
"YES" to update the IP address.
Important: the controller is not accessible directly on the
internet as a fi rewall guarantees remote access only via a secure
connection (Carel tERA cloud or encrypted VPN connection).
7.9.5
Supervisor settings for ModBus or BACnet on
TCP/IP (Ethernet port) (Installer menu)
Both Modbus and BACnet are available on the Ethernet port; to enable
the protocol go to screen Eh05:
Index
Description
Parameter
Eh05
Supervision
Select the protocol on the Ethernet port.
En. ModBus TCP/IP: Enabled/Disabled
settings on
Ethernet port
En. BACnet TCP/IP: Enabled/Disabled
Defaults:
En. ModBus TCP/IP: Disabled
En. BACnet TCP/IP: Enabled
Note: only one instance of the BACnet protocol is available,
therefore it is not possible to activate BACnet on the BMS port and on
the Ethernet port at the same time.
7.10 E. Settings - i. Logout
7.10.1
Logout from the settings menu (Installer menu
and Service)
Screen Ei01 is used to exit the Settings menu. The screen also describes
the type of login performed (installer or service).
When accessing this screen, the following information will be shown (in
the currently selected language).
To logout press "ENTER".
The main screen will then be displayed.
Press "ESC" to exit if not wanting to end the session.
41
"heaterSteam" +0300080EN - rel. 1.0 - 27.04.2016