Steam Production Control Signals - Carel heaterSteam User Manual

Electric resistance humidifier
Hide thumbs Also See for heaterSteam:
Table of Contents

Advertisement

4.5 Steam production control signals

The humidifi er features solid state relays (SSR) for modulating steam
production, and consequently capacity may range from 1 to 100% of output,
depending on control requirements. The humidifi er can be connected via
RS485 serial or Ethernet connection to a remote supervisor. Depending on
the type of signal used, steam production can be enabled and/or managed
in diff erent ways (ON/OFF or modulating).
Important: the probe inputs are protected against short-circuits,
and the maximum current delivered (M2.3) is 50 mA. Despite this, it is
recommended to confi gure the "Control type" before connecting the
probes to the terminals.
To help users confi gure the unit, a screen index is shown at the top right of the
display. The screen index corresponds to the sequence in each menu in order
to reach the specifi c page.
Fig. 4.n
Steam production can be started by:
HUMIDISTAT (ON/OFF operation):
connect terminals M2.1 and M2.2 (production request) to a humidistat;
short-circuit terminals M2.7 – M2.8 (jumper) to enable production;
to enable ON/OFF operation, set:
Screen index
Screen description
Ea01
Control type
Ea04
Maximum production
M9
1
2
1
2
Fig. 4.o
_________________________________________________________
HUMIDISTAT and REMOTE CONTACT (ON/OFF operation)
connect terminals M2.1 and M2.2 (production request) to a humidistat;
connect inputs M2.7 – M2.8 (enable) to a remote contact (e.g.: switch,
timer,...);
to enable ON/OFF operation, set:
Screen index
Screen description
Ea01
Control type
Ea04
Maximum production
M9
1
2
1
2
Fig. 4.p
Screen
index
Parameter
External ON/OFF signal
0-100% of rated production
M2
M8
3
4
5
6
7
8
1
2
Parameter
External ON/OFF signal
0-100% of rated production
M2
M8
3
4
5
6
7
8
1
2
Steam production can be enabled and controlled by:
EXTERNAL PROPORTIONAL CONTROLLER (modulating operation)
short-circuit terminals M2.7 – M2.8 (jumper) to enable production;
connect terminals M2.1 and M2.2 (production request) to an external
controller;
to enable control, set:
Screen ind.
Screen desc.
Ea01
Control type
Ea03
Proportional band
Ec01
Main probe type
M9
1
2
1
_________________________________________________________
EXTERNAL PROPORTIONAL CONTROLLER and REMOTE CONTACT
(modulating operation)
connect terminals M2.1 and M2.2 (production request) to a humidistat;
connect inputs M2.7 – M2.8 (enable) to a remote contact (e.g.: switch,
timer,...);
to enable control, set:
Screen ind.
Screen desc.
Ea01
Control type
Ea03
Proportional band
Ec01
Main probe type
M9
1
2
1
_________________________________________________________
EXTERNAL PROPORTIONAL CONTROLLER and REMOTE CONTACT
(modulating operation) with LIMIT PROBE
short-circuit terminals M2.7 – M2.8 (jumper) to enable production;
alternatively connect terminals M2.7 – M2.8 to a remote contact (e.g.:
switch, timer,...);
connect terminals M2.1 and M2.2 (production request) to an external
controller;
connect the active limit probe to terminals M2.5, M2.3 (+12Vdc), M2.6
(GND);
to enable control, set:
21
"heaterSteam" +0300080EN - rel. 1.0 - 27.04.2016
Parameter
proportional to external signal
Set: Hysteresis (0-100%)
Minimum production (0-100%)
Maximum production (0-100%)
Select from: 0-1V, 0-10V, 2-10V, 0-20mA,
4-20mA
M2
M8
2
3
4
5
6
7
8
1
2
Fig. 4.q
Parameter
proportional to external signal
Set: Hysteresis (0-100%)
Minimum production (0-100%)
Maximum production (0-100%)
Select from: 0-1V, 0-10V, 2-10V, 0-20mA,
4-20mA
M2
M8
2
3
4
5
6
7
8
1
2
Fig. 4.r
ENG