CONTROL WITH TWO ACTIVE TEMPERATURE PROBES
short-circuit terminals M2.7 – M2.8 (jumper) to enable production;
alternatively connect terminals M2.7 – M2.8 to a remote contact (e.g.:
switch, timer,...);
connect the main active room probe to terminals M2.1, M2.2 (GND)
and M2.3 (+12Vdc);
connect the second active probe to terminals M2.5, M2.3 (+12Vdc) and
M2.6 (GND);
to enable control, set:
Screen ind.
Screen desc.
Ea01
Control type
Ea02
Control with 2 probes Set the weight of the two probes (0-100%)
Ea05
Modulating control
Ec01
Main probe type
Ec02
Second probe type
The controller will calculate the weighted average between the two
probes. The weight of the two probes can also be set.
M9
1
2
1
OUT H / T
M
+ (G)
OUT H / T
M
+ (G)
The following probes can be connected:
CAREL probes for rooms
for air ducts
for technical applications
Note:: non-CAREL active probes can be connected to the controller.
_________________________________________________________
CONTROL WITH ONE NTC TEMPERATURE PROBE (passive)
short-circuit terminals M2.7 – M2.8 (jumper) to enable production;
alternatively connect terminals M2.7 – M2.8 to a remote contact (e.g.:
switch, timer,...);
connect the main NTC room probe to terminals M2.1, M2.2;
to enable control, set:
Screen index
Screen description
Ea01
Control type
Ea05
Modulating control
Ec01
Main probe type
M9
1
2
1
"heaterSteam" +0300080EN - rel. 1.0 - 27.04.2016
Parameter
Temperature (two probes)
Set: temperature set point (0-100 °C) (32-
212°F)
diff erential (2-20°C) (3.6-36°F)
Minimum production (0-100%)
Maximum production (0-100%)
Select from: 0-1V, 0-10V, 2-10V, 0-20mA,
4-20mA
Select from: 0-1V, 0-10V, 2-10V, 0-20mA,
4-20mA
M2
M8
2
3
4
5
6
7
8
1
2
Fig. 4.aa
DPWC111000
DPDC110000; DPDC210000
DPPC210000, DPPC210000
parameter
one temperature probe
Set:
temperature set point (0-100 °C)
(32-212°F)
diff erential (2-20°C) (3.6-36°F)
Minimum production (0-100%)
Maximum production (0-100%)
Set probe type: NTC
M2
M8
2
3
4
5
6
7
8
1
2
Fig. 4.ab
CONTROL WITH TWO NTC TEMPERATURE PROBES (passive)
short-circuit terminals M2.7 – M2.8 (jumper) to enable production;
alternatively connect terminals M2.7 – M2.8 to a remote contact (e.g.:
switch, timer,...);
connect the main NTC room probe to terminals M2.1, M2.2;
connect the second NTC probe to terminals M2.5, M2.6;
to enable control, set:
Screen index
Screen description
Ea01
Control type
Ea02
Control with 2 probes
Ea05
Modulating control
Ec01
Main probe type
Ec02
Second probe type
The controller will calculate the weighted average between the two
probes. The weight of the two probes can also be set.
M9
1
2

4.8 Alarm contact

The humidifi er controller is fi tted with a relay contact for remote signalling
of one or more faults or alarms. The alarm contact (250 Vac; max capacity: 2
A resistive - 2 A inductive) is connected to terminals M6.1, M6.2 and M6.3.
M12
3
M6.1
CO - Alarm common
M6.2
NC - NC alarm contact
M6.3
NO - NO alarm contact
24
parameter
Modulation with two temperature
probes
Set the weight of the two probes
(0-100%)
Set:
temperature set point (0-100 °C)
(32-212°F)
diff erential (2-20°C) (3.6-36°F)
Minimum production (0-100%)
Maximum production (0-100%)
Set probe type: NTC
Set probe type: NTC
M2
M8
1
2
3
4
5
6
7
8
1
2
Fig. 4.ac
M1
M5
M6
2
1
1
2
1
2
1
2
3
L N
Fig. 4.ad