User manual NO POWER & SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT! H i g h E f f i c i e n c y S o l u t i o n s...
Page 3
The customer (manufacturer, developer or installer of the final equipment) the product, even if CAREL INDUSTRIES Hq or its subsidiaries are warned of the accepts all liability and risk relating to the configuration of the product in order possibility of such damage.
(**) Important: for conductivity values around “0”, contact CAREL readings or the external controller, it will activate and control the INDUSTRIES for operating suggestions. distribution and atomisation system so as to maintain the humidity or temperature level.
INSERTI FILETTATI M6 FEMMINA M6 F Fig. 1.i Fig. 1.k Important: the maximum distance between the cabinet and rack/ distribution system is 50 metres, for higher distances contact CAREL INDUSTRIES. Positioning procedure: • after opening the packaging: • position the cabinet in the final position;...
External stainless steal pipe φ 10 mm/ 0.4 inch tray Tab. 2.b N.B.: the hose and the clamp are not supplied by CAREL, to tighten clamp, lift the cabinet. connect the drain bypass “6” Fig. 1.a to the drain system.
Field card input for Master Slave connection Serial Card Serial card input for BMS (Building Management Systems) Fig. 3.a N.B.: feature adequate protection on all activation Slave version outputs to external devices. Fig. 3.b “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Remote ON/OFF RKEN (enable slave rack) NC/NO N.B.: the Master unit is supplied with contacts PEN-G0A and RKEN- G0A jumpered, the Slave unit is supplied with contact RKEN-G0A jumpered “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
UAKDER6000. humiFog cabinet Ambient temperature probe + limit humi- dity probe OUT T (main) N.B. For electrical distances greater than 30 m contact Carel. OUT H (limit) +Vdc +(G) h. Modulating control with temperature control and limit humidity and temperature probe (TT/TH control) 0 to 1 V;...
“open”, free contact “closed”. noid valves Tab. 3.c N.B.: using the solenoid valves supplied by Carel SpA, each individual cabinet can power up to 22 solenoid valves, divided as follows: • 10 NC capacity-control solenoid valves •...
(Remote Actuator) • Allow the slave cabinet to use a rack with 6 NC valves on step 1 and 4 Fig. 3.v NC valves on step 4. “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Default: CAREL supervisor protocol. establishes if it is required to expand and alerts the user via a dedicated pop-up window • Configure the slave used for the expansion as “Expansion/Remote actuator 1” “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
The flow control configuration guarantees maximum humidification and same time without installing a pumping unit for each AHU or industrial adiabatic cooling precision as capacity is controlled continuously and environment. across a wide range. “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Note that a droplet collector tank with drain connection must also be fitted, containing the rack, droplet evaporation chamber and droplet separator. This tank is not supplied by CAREL. “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
6.1 Main advantages of humiFog multizone The main characteristic of humiFog for AHUs is compliance with the European standards on air hygiene, as certified by the Institut für Lufthygiene in Berlin, which has declared it as compliant with the...
(for example, not external request near windows or the nozzles where the cooling and humidification effect maximum production do not correspond to the averages in the room) minimum production “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
This is the typical configuration when the control is entrusted to a • a digital contact or Building Management System that generates a control signal. • a digital variable via supervision (DIG 63). “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 26
Pmax 100% H=10%Band °C/°F % Fan Band Fig. 7.h Pmax 100% H=10%Band %RH or % Opening Band Fig. 7.i “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
S= capacity of step T M= rack capacity T= index of the step, 1 to N N= step number N.B.: the maximum flow-rate of one step is 120 l/h. “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
For the configuration of the steps, see the instructions provided in the previous paragraph “Single zone applications in AHUs – constant pressure control” and “Single zone applications in rooms”. “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 29
REVERSE OSMOSIS system; Key: drain valves (one in each zone); water from REVERSE OSMOSIS system; fill valve; air handling unit; ambient probe; main drain valve main drain valve. “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Obviously, pressure relief must be enabled, otherwise each rotation would require a filling cycle. humiFog multizone independently manages the production of pressurised water, the distribution and filling, drain and wash cycles. This paragraph illustrates the latter functions.
Press ENTER to select the desired language. Once finished press ESC to return to the startup procedure. This screen is displayed for 60 seconds. “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Bypass temp. [°C/°F] Temperature of the water recycled in the pump Rack temp. [°C/°F] Temperature detected by the probe in the ato- mization area (optional). Setpoint set from CTA “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 34
ENTER to confirm and move the cursor to the next value that are solved. • ESC to return to the installer menu. Ref. Parameter number, hour and date of warning/alarm Description of warning/alarm “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 35
Start Defines the start of the daylight saving time period Defines the end of the daylight saving time period “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 36
first 50 hours of operation, which is not restored following the simple reset of the hourmeter on the Cf02 screen. “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 37
Note: if the washing parameter was set to “Periodic” or “Daily”, a washing will be performed at every start of the pumping station. “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 38
ROEN-COM contact. Open contact ON pump (if the set parameter is N.A., otherwise vice versa) Closed contact OFF pump (if the set parame- ter is N.A., otherwise vice versa) “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 39
Correlates the maximum value of the humidity/temperature with the minimum value of the main signal --100 ... +100 %/° Offset Humidity correction factor read by the main signal -20 ... +20 %/° “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 40
Display Description Range De- Unit fault Collectors Set the number of vertical collec- number tors dedicated to each single step (as shown in the documentation attached to the rack) “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 41
Set to “YES” if you want to enable YES-NO present the environment atomization of the pumping station with the use of ventilating heads “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 42
Fig. 10.a Time If the rotation is enabled 0 - 8 define the Function time of the pump after which the pump is rotated “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 43
Screen visible only to ensure address the compatibility with previous versions of humiFog (*) the humiFog is provided with an alarm input for water treatment, thus the machine is enabled. “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 44
10.9 Menu manutentore c. Zone remote - zone remote 01 Important: the operations described in this menu must only be Remote area configuration carried out by authorised Carel personnel From the main screen press: • PRG to access the main menu;...
Page 45
(-> = Open, - = closed) Insert new Defines the new password of Drain solenoid valve status step 1-6 maintenance the maintainer menu (| = Open, - = closed) password “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 46
Air handling unit flow switch status 12- FLUX Backup req. Backup sign of life relay setting Fill solenoid valve status setting Fill Ev. Drain solenoid valve status setting in SmartZ. “SmartZone” mode Drain “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 47
Flow lb/h Ref. Display Description Ran- Def. Unit Reset Resetting the hourmeter for Si/No pump pump operation counter Last View the date of the last gg/mm/aaaa reset resetting date “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 48
Zona xxx offline The history contains 200 alarms, the older ones being overwritten. “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Stop produc- cabinet pump inlet lower than 2°C proper dimensioned heater tion High pressure alarm from Flow pressure excee- Contact CAREL for instructions on checking the Manual Active Stop produc- the pressure switch ding 90 bar conditions of the bypass valve...
Page 50
Humifog adjustment is enabled by not received requests the supervisor for more than 30 seconds. “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
Page 51
(Bbc05 screen), the production reduction feature is disabled “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...
12.5 Wiring diagram humiFog multizone - Slave - CE 24 (GB) 24 (GB) 24V [GA] 0 [G0A] TR-B TR-A F3 F4 F1 F2 GR N L TORQUE FORCE TERMINALS (Nm) SINGLE TERMINAL: 0,6 min -> 0,8 max DOUBLE TERMINAL: 0,6 min -> 0,8 max TERMINAL WITH FUSE: 1,5 min ->...
Page 61
F3-F4 -> 4A F 5x20 600V -> 4A T 5x20 250V F9 -> 16A T 10,3x38 500V FORZA DI SERRAGGIO MORSETTI pCO5+ TORQUE FORCE TERMINALS pCO5+ (Pound Inches) = 0,5 min -> 0,6 max “humiFog multizone - pumping unit” +0300066EN - rel. 1.2 - 10.12.2015...