Ultrasonic humidiers ventilation - duct version User manual NO POWER & SIGNAL CABLES TOGETHER READ CAREFULLY IN THE TEXT!
Page 3
2012/19/EU issued on 4 July 2012 and related national legislation, please note that: user manual, may cause the fi nal product to malfunction; CAREL accepts no liability in such cases. 1. Waste Electrical and Electronic Equipment (WEEE) cannot be disposed of as municipal waste...
□ make sure the humidifier is intact upon delivery and immediately Range of ultrasonic adiabatic humidifiers for direct humidification in ducts or air handling units. humiSonic is particularly suitable for many notify the transporter, in writing, of any damage that may be due to applications in which optimisation of room humidity is an essential careless or improper transport;...
1.10 Operating principle 1.11 Accessories • The operation of humiSonic humidifiers is based on the principle of BMS/RS485 serial card (P/N PCOS004850): to be installed on the control atomisation of demineralized water using ultrasound technology. The board on the ““Main”” panel, used for direct interface to an RS485 humidifier operating principle can be summarised as follows: network, with a maximum baud rate of 19200.
Should on the other hand the humidifier be fed with treated water from a Total air flow-rate introduced HU Humidifier Carel reverse osmosis system connected to potable water, the dual check CD Combined dampers DP Condensate collection tank valve shall be installed in the supply line to the reverse osmosis system.
Fig. 2.d and, if necessary, the washing cycle, while the WTS production time must cover humiSonic production demand and fi ll the vessel as quickly as Note: OD = 8 mm (5/16”), ID = 6 mm (15/64”) possible.
OFF: 19200 ON: 9600 Reserved Reserved Transducer production management OFF: --> parallel ON: --> series Fig. 3.a Note: to avoid unwanted interference, power cables should be kept separate from probe signal cables. “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
OUT = 48 V DC 3,15 A T - 48 V + 48 V 24 V PRI: COM: 120 SEC: BL - YL 24 V 75 VA 50/ 60 Hz CLASS 2 Fig. 3.h “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
11,5 Kg / 25,4 lbs UQ18CD0000 Main Electrical Panel 1200 W -230 V 11,5 Kg / 25,4 lbs glands (installer’s responsibility) Cable glands Control board Air intake openings Power supply ON/OFF switch “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
24 V PRI: COM: 120 SEC: BL - YL 24 V 75 VA 50/ 60 Hz CLASS 2 POWER POWER SUPPLY SUPPLY + 48 V - 48 V POWER SUPPLY Fig. 3.m “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
Note: in industrial environments (IEC EN61000-6-2) the signal cables leaving the unit must not exceed 10 m (33 ft) in length: remote on/off digital input (ON/OFF - COM terminals) and shielded cable for RS485 communication. “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
Set parameter Fa04 for the type of signal from the temperature probe: type = 0 to 1V, 0 to 5V. Probe type = 0 to 1V, 0 to 5V, 0 to 10V, NTC. “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
The washing Opening the COM-ONOFF contact (enabling signal); • cycle is run after default 24 hours (continuous) of no operation, i.e. the Active alarms; • humidifier is in standby. Via network. “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
4 Control type selected 9 Maintenance required 5 Unit status 10 Time bands enabled Tab. 5.d Note: the control type is selectable in user menu F, under screen Fa01: Regulation. See the parameter table. “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
(+limit humidity PW1(0077). set point); d: BMS configuration: set BMS communication protocol (CAREL, Modbus), C: Clock/scheduler: set the current time and date (C01), the date for communication speed, network address, enable control serial.
2. activate production by one group of transducers (mist1/ mist 2) or the valve in standby is selected as open. both; 3. activate the alarm relay Screen index Display description Fc03 Settings Drain valve in stand-by Open Closed Open Tab. 6.c “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
19200 1200 19200 Fig. 6.a Address Gd02 BMS configuration Serial manager Disabled Disabled Enabled - Tab. 6.l Input Input signal Input value for min. request Request Input value for max request Offset “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
FILL 1 V, 0 to 5V, 0 to 10V) and is limited based on the value measured by the limit humidity probe. This is the typical configuration for humiSonic Fig. 7.a installations connected to a Building Management System that provides a control signal.
Atomised water flow-rate is modulated between the minimum and maximum rated capacity. Screen index Display description Fa02 Regulation Max prod Min prod Fa11 Regulation Mist modulation Series Series Parallel - mode Mist modulation period Tab. 7.d “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
Only if ready ? Tab. 7.e The washing cycle can only be performed if humiSonic is operating (only if ready ? = YES), or if it is operating or in standby (only if ready ? = NO). It is assumed that the humidifier is not operating because it is disabled (see ON activation conditions).
1200 Empty drain T. 1200 Screen index Display description Def Tab. 7.m Fb08 From request *: Depending on humiSonic size, see previous tables. When request Rise Rise Fall Tab. 7.l 7.7.2 Production, refilling times Tmax prod: maximum atomised water production time (drivers active), during which the level sensor must signal low water level.
Page 30
Tmin prod Tab. 7.o the water refill time is further increased (100% more than Refill time) *: Depending on humiSonic size, see previous tables. and chattering* of the drain solenoid valve is activated during the first automatic washing cycle; Low lev delay: low level filtering time for activating the fill cycle.
¦ Probe T ¦ Probe T+Limit rH% Unit of measure °C-Kg/h °C-Kg/h °F-lb/h °C-Kg/h ¦ °F-lb/h Fa02 Regulation Max Prod Max Prod Min Prod Fa03 Regulation Ambient probe Analog Analog HYHU000000 Analog ¦ HYHU000000 “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
Page 32
Production Maintenance Production ¦ Maintenance Logic N.O. N.O. N.C. Fc03 Settings Drain valve in stand-by(*) Open Open Closed Drain delay in stand-by (*)=Open Service Change language Language Italian English Italian System information “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
Page 33
Off ¦ On Gf03 Manual management Mist 1 No ¦ Yes Mist 2 No ¦ Yes Alarm relè Off ¦ On Gf04 Manual management Ambient probe 1000 Limit probe 1000 Tab. 8.a “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
8.1 Supervisor variable list The interface to an RS485 supervisor network using the Carel/Modbus protocol with a maximum baud rate of 19200 bps requires installation of the optional opto-isolated card PCOS004850 and the plastic support PCOS00S030 that fixes the optional card to the electronic control board slot on the “Main”...
Page 35
Scheduled wash hours Fb06 Scheduled wash minutes Fb06 Scheduled wash weekday Fb06 Request from BMS serial Main board offline time Gea05 Preheat probe alarm delay Fa12 Supervisor control type Gd02 Tab. 8.d “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
Fill valve fault Water is filled even after switching off the Replace the fill valve appliance Tab. 9.c “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
11 Sensore di livello UUKLV00000 interno vasca Tab. 10.b Fig. 10.b Note: maintenance on the humidifi er must be carried out by CAREL technical service or other professionally qualifi ed personnel “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
An operating hour counter (eff ective production) and a unit operating hour counter (total hours) can be set, Fig. 10.e together with a maintenance hour counter, after which the display shows a warning message. See alarm CL. “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
Remove the boards in the same way as described for the front driver board. 10.8 Cleaning the tank Proceed as shown previously to remove the side panels and top cover with the diff users. To clean the tank, use a soft brush. “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
0 to 5V, 0 to 10V Maximum load 2 kΩ (5 mA) Precision ±3 % of full scale Environmental conditions Ambient operating temperature °C (°F) 1 to 40 (33.8 to 104) Ambient operating humidity (% rH) 10 to 80 Tab. 11.b “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
It is necessary to install on and handled only by the Main who shall then adjust the operation of the humiSonic “Main”, the auxiliary board cod. UUKAX00000 at available the Secondary. The production level of the Main is replicated by all the space on board the electronic board identified as no.
Set the type of signal PR% output from the Main 1 panel, either 0-5V and 0-10V (screen Fa14) and set the input signal to the other Main panels accordingly (screen Fa04, Probe type). Fig. 12.c “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
Page 46
OUT H/T (0 to 1 VDC, (G+) (G+) 0 to 5 VDC) NTC probe MAIN (2) MASTER (2) Complete panel terminal block Alarm Power Supply Serial connection until n.4 MASTER MAIN Fig. 12.d “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...
(3,1) (3,5) (3,1) (11,81) water drain basin Fig. 13.b Key: Humisonics total dimention Absorption distance Total length For proper sizing and placement of Humisonic within the duct , contact Carel support “humiSonic ventilation” +0300063EN - rel. 1.3 - 14.05.2021...