3.6 Outlet pressure limits

The backpressure at the boiler outlet, either positive or negative, depends
both on the relative pressure in the duct/AHU and the pressure drop in
the steam pipe, due to bends or adapters, and the steam distributor.
Carel steam transport pipes have a pressure drop of around 150 Pa/m
(0.021psi) (respecting the maximum fl ow-rate recommended by Carel).
Carel DP* series linear distributors have a pressure drop of around 25 Pa
(0.003psi) (respecting the maximum fl ow-rate recommended by Carel).
Considering these values, the boiler outlet pressure must be:
boiler outlet pressure > 150 [Pa/m] * steam pipe length [metres] + 25 [Pa]
DP + pressure in duct/AHU [Pa]
Boiler outlet pressure values for heaterSteam:
UR002...R013
pressure limits at boiler outlet
0 to 1500 (0 to
Pa (PSI)
0.218)
Note: a pressure of around -200 Pa (-0.029 psi) at the boiler outlet
corresponds to around 20 mm (0.78") of water inside the boiler (for all
sizes).