11.1 Supervisor network protocols and
confi guration
The humidifi er can be connected to a supervisor via serial (BMS) or
Ethernet network. The Carel, ModBus and BACnet protocols are supported
as standard by the units.
M9
M2
M8
1
2
1
2
3
4
5
6
7
8
1
2
Fig. 11.a
Port
Terminal on c.pHC controller Protocol
BMS (1)
M12.1, M12.2, M12.3
Ethernet (2)

11.2 Table of supervisor variables

The variables shown in the lists below are only a set of all the internal variables on the heaterSteam humidifi er.
DO NOT CONFIGURE ANY VARIABLES THAT ARE NOT SHOWN IN THE TABLES TO AVOID RISKING INCORRECT HUMIDIFIER OPERATION.
11.2.1
Table of Carel variables
Below are the variables used by the Carel protocol.
Integer variables
Variable
Variable name
1
SV_SWVer
2
SV_OSVer
3
UnitModel
4
Conductivity
5
WirelessPrbInfo_1.BattLev
6
WirelessPrbInfo_1.RadioSignalLev
7
WirelessPrbInfo_2.BattLev
8
WirelessPrbInfo_2.RadioSignalLev
9
WirelessPrbInfo_3.BattLev
10
WirelessPrbInfo_3.RadioSignalLev
11
WirelessPrbInfo_4.BattLev
12
WirelessPrbInfo_4.RadioSignalLev
13
UnitStatus
14
WorkHr
15
CylWorkHr
19
RegulationCfg.RegTyp
20
ThrshAlrmDT
21
MainPrbCfg.Typ
22
LimitPrbCfg.Typ
23
WHardnessMan
24
EvapCycleNoThrshsh
25
FillTScale
26
DilDrainTScale
27
Scheduler.SchedDayToSet
28
SchedDayCfg[0].StartHr
29
SchedDayCfg[0].StartMin
30
SchedDayCfg[0].WorkMode
31
SchedDayCfg[1].StartHr
32
SchedDayCfg[1].StartMin
33
SchedDayCfg[1].WorkMode
34
SchedDayCfg[2].StartHr
35
SchedDayCfg[2].StartMin
36
SchedDayCfg[2].WorkMode
37
SchedDayCfg[3].StartHr
38
SchedDayCfg[3].StartMin
39
SchedDayCfg[3].WorkMode
40
SchedDayCfg[4].StartHr
41
SchedDayCfg[4].StartMin
42
SchedDayCfg[4].WorkMode
43
SchedDayCfg[5].StartHr
44
SchedDayCfg[5].StartMin
45
SchedDayCfg[5].WorkMode
46
UoM

11. SUPERVISOR NETWORK

M12
M1
M5
M6
3
2
1
1
2
1
2
1
2
3
Ethernet
1
2
Carel, ModBus, BACnet, Carel retro
ModBus, BACnet
Tab. 11.a
R/W
R
R
R
R
R
R
R
R
R
R
R
R
R
R
R
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
RW
To confi gure supervision on the BMS port (1), go to "SETTINGS –
SUPERVISION", specifi cally screens Eh01, Eh02 and Eh03.
If connecting the supervisor to the Ethernet port (2), set the network
parameters (DHCP, IP address, subnet mask, gateway, DNS) on screen
Eh04.
For other supervisor protocols, select the Carel protocol on the BMS serial
port and use the Carel external gateway (supernode for humidifi cation:
SNU0000EM0) combined with the desired supervision card (depending
on the protocol).
Note: Ethernet CAT-5 STP cable, maximum length 100 m. To connect
the shield, use the earth connector provided on the controller.
Note: for BMS and Fieldbus, use shielded cables with the shield
connected to earth.
Description
Software version
OS version
Model version
Conductivity
Wireless probe 1: battery level
Wireless probe 1: wireless signal level
Wireless probe 2: battery level
Wireless probe 2: wireless signal level
Wireless probe 3: battery level
Wireless probe 3: wireless signal level
Wireless probe 4: battery level
Wireless probe 4: wireless signal level
Unit status
Unit operating hours
Cylinder operating hours
Control type
High humidity/temperature alarm delay
Main probe type
Limit probe type
Manual water hardness value (if WHardnessTyp is TRUE)
Number of evaporation cycles (0=auto)
Variation in fi ll time
Variation in drain time
When >0, day of the week to be confi gured (1=Monday, 7=Sunday)
Band 1 start hours
Band 1 start minutes
Band 1 operating mode
Band 2 start hours for
Band 2 start minutes
Band 2 operating mode
Band 3 start hours
Band 3 start minutes
Band 3 operating mode
Band 4 start hours
Band 4 start minutes
Band 4 operating mode
Band 5 start hours
Band 5 start minutes
Band 5 operating mode
Band 6 start hours
Band 6 start minutes
Band 6 operating mode
Unit of measure
47
Category
Unit info
I/O
Wireless probes
Unit status
Reg
Alrm T
Probes cfg
Unit cfg
Scheduler setting
UoM
"heaterSteam" +0300080EN - rel. 1.0 - 27.04.2016
ENG