Control With Humidity Probes - Carel heaterSteam User Manual

Electric resistance humidifier
Hide thumbs Also See for heaterSteam:
Table of Contents

Advertisement

ENG
Screen ind.
Screen desc.
Ea01
Control type
Ea03
Proportional band Set:
Ea06
Limit probe
Ec01
Main probe type
Ec02
Limit probe type
M9
1
2
1
OUT H / T
M
+ (G)
Note: in industrial environments (IEC EN61000-6-2) the signal cables
leaving the unit must not exceed 30 m (98') in length: steam production
signal cable (terminals M2.1, M2.2), digital remote on/off input (terminals
M2.7, M2.8) and shielded cable for RS485 communication.

4.6 Control with humidity probes

The main control board, connected to a room humidity probe, manages
steam production based on the humidity measured. A second outlet
humidity limit probe can also be connected: with this confi guration,
typical of air handling units, the main control board continues managing
steam production according to the humidity requirement, however
production is limited according to the relative humidity measured in the
outlet duct.
HP
Key:
HP
Humidity control probe (intake/room humidity probe)
HLP
Limit humidity probe (outlet humidity probe)
Remote Contact Remote contact
"heaterSteam" +0300080EN - rel. 1.0 - 27.04.2016
Parameter
prop. to external signal with limit probe
Hysteresis (0-100%)
Minimum production (0-100%)
Maximum production (0-100%)
Set:
Set point (0-100 %rH)
Diff erential (0-100%)
Select from: 0-1V, 0-10V, 2-10V, 0-20mA,
4-20mA
Select from: 0-1V, 0-10V, 2-10V, 0-20mA,
4-20mA
M2
M8
2
3
4
5
6
7
8
1
Fig. 4.s
HLP
Remote
Contact
Fig. 4.t
CONTROL WITH ONE HUMIDITY PROBE
short-circuit terminals M2.7 – M2.8 (jumper) to enable production;
alternatively connect terminals M2.7 – M2.8 to a remote contact (e.g.:
switch, timer,...);
connect the main active room probe to terminals M2.1, M2.2 (GND)
and M2.3 (+12Vdc);
to enable control, set:
Screen ind.
Screen desc.
Ea01
Control type
Ea05
Modulating control
2
Ec01
Main probe type
OUT H / T
_________________________________________________________
CONTROL WITH ONE HUMIDITY PROBE AND LIMIT PROBE
short-circuit terminals M2.7 – M2.8 (jumper) to enable production;
alternatively connect terminals M2.7 – M2.8 to a remote contact (e.g.:
switch, timer,...);
connect the main active room probe to terminals M2.1, M2.2 (GND)
and M2.3 (+12Vdc);
connect the active limit probe to terminals M2.5, M2.3 (+12Vdc), M2.6
(GND);
to enable control, set:
Screen ind. Screen desc.
Ea01
Control type
Ea05
Modulating
control
Ea06
Limit probe
Ec01
Main probe type Select from: 0-1V, 0-10V, 2-10V, 0-20mA, 4-20mA
Ec02
Limit probe type Select from: 0-1V, 0-10V, 2-10V, 0-20mA, 4-20mA
OUT H / T
OUT H / T
The following probes can be connected:
CAREL probes for rooms
for air ducts
for technical applications
Note: non-CAREL active probes can be connected to the controller.
22
Parameter
one humidity probe
Set:
humidity set point (0-100 %rH)
diff erential (2-20%rh)
Minimum production (0-100%)
Maximum production (0-100%)
Select from: 0-1V, 0-10V, 2-10V,
0-20mA, 4-20mA
M9
M2
1
2
1
2
3
4
5
6
7
M
+ (G)
Fig. 4.u
Parameter
humidity with limit probe
Set:
humidity set point (0-100 %rH)
diff erential (2-20%rh)
Minimum production (0-100%)
Maximum production (0-100%)
Set point (0-100 %rH)
Diff erential (0-100%)
M9
M2
1
2
1
2
3
4
5
6
7
M
+ (G)
M
+ (G)
Fig. 4.v
DPWC111000
DPDC110000, DPDC210000
DPPC210000, DPPC210000
M8
8
1
2
M8
8
1
2

Hide quick links: