9.1 Integrated web server

The integrated web server is used to confi gure and monitor the main
unit parameters directly from a PC. In fact, using the Ethernet port on
the humidifi er controller, the unit can be accessed via a local network by
simply entering its IP address in the browser.
To log in and access the various menu items, use the installer or service
password (see paragraph 6.12 "Main menu").
Note: the web server is managed in the heaterSteam titanium
version.

9.2 Connecting to the integrated web server

For the physical connection to the controller from a PC, must use the RJ45
Ethernet port on the c.pHC and an Ethernet category 5 cable.
Fig. 9.b
The Ethernet port is available on the humidifi er's c.pHC controller:
M9
M2
M8
1
2
1
2
3
4
5
6
7
8
1
2
The PC and the humidifi er controller (or all controllers, for Master/Slave
systems) must be part of the same subnetwork.
The default network confi gurations for the c.pHC are:
unit's IP address: 192.168.0.1
subnet mask: 255.255.255.0
gateway: 192.168.0.1
For example, the PC's network settings can be changed as follows:
unit's IP address: 192.168.0.2
subnet mask: 255.255.255.0
gateway: 192.168.0.1
To do this, access the "Network and sharing center" on the PC and go to
"Local network connection". Then modify the addresses, as shown above,
for Internet protocol version 4.
Each c.pHC controller can obviously also be added to the Ethernet local
network, allowing the web server to be accessed from any point in the
network and for each humidifi er.

9. WEB SERVER

Fig. 9.a
M12
M1
M5
M6
3
2
1
1
2
1
2
1
2
3
Ethernet
Fig. 9.c
Important: the controller is not accessible directly on the internet
as a fi rewall guarantees remote access only via a secure connection (Carel
tERA cloud or encrypted VPN connection).

9.3 Description of the web server function

The web server "Home" page provides access to the display, so as to carry
out all the confi guration operations in the same way as if working directly
on the pGD. In addition, there will be an immediate response from unit
concerning its operation in the network.
The main confi gurations and information are:
UNIT
NETWORK
MAINTENANCE
INFO
Unit menu
Probes: information and confi guration of the main and limit probe.
Select the type of signal and defi ne the minimum and maximum values.
Wireless: enable and associate each wireless probe to the main probe
group or limit probe group. Read the humidity and/or temperature, level
and battery status.
Control: select the control type. Set the set point, diff erential, minimum
and maximum.
Confi guration: confi gure the time and date. Confi gure the main alarms
and variation in percentages of fi ll and drain times.
Scheduler: enable and set the daily and weekly time bands.
Network menu
Display a summary of the status of the units in the advanced Master/
Slave system.
Maintenance
Timers: display cylinder and unit operating hours. Display the time
remaining until maintenance is required and set the maintenance pre-
alert.
Logs: display the log of main variables (production, set point, drain pump
status, fi ll valve status, request, unit status).
Live: real time display of the main variables (production, set point, drain
pump status, fi ll valve status, request, unit status).
Info
Unit info: information on the unit model and software version. Select
language and unit of measure.
Resources: useful links (Carel website, heaterSteam manual and page on
Carel website).
Guide & FAQ: general information on using the web server.
Note: to avoid incorrect settings, some of the main unit operating
parameters can only be modifi ed via the web server when the unit is off
(off from keypad).