Application; Outdoor / Patio; Indoor Installation - Schwank InfraSave 2100 Owner's Manual

Patio heater for outdoor application and gas-fired high intensity infrared heater for commercial / industrial non-residential indoor spaces
Hide thumbs Also See for InfraSave 2100:
Table of Contents

Advertisement

alfresco-heating.com
1. APPLICATION: This gas-fired infrared heater is suitable for installation for heating of out-
door commercial / industrial / residential areas and indoor commercial / industrial / non-
residential spaces.
It is beyond the scope of these instructions to consider all conditions that may be encountered.
Installation in the USA must conform to all local and national code requirements including the
current National Fuel Gas code ANSI Z223.1, and the National Electrical Code ANSI/NFPA No
70 (latest edition). All installations in Canada must conform to local and national code require-
ments including, CAN/CGA-B149.1 installation code for gas burning appliances and equipment
and the Canadian Electrical Code PART 1 CSA C22.1 (latest edition). In case of discrepancy
due to revisions to standards and codes, the latest standards, codes, and installation manual
are in effect and take priority.
DO NOT INSTALL THIS APPLIANCE IN A RECESS, ALCOVE, OR ENCLOSURE.
Adequate free space must be provided to allow the products of combustion to escape from the
heater to atmosphere when installed outdoors, or to mechanical exhaust withdrawal when in-
stalled indoors. Also refer to "Outdoor" and "Indoor" definitions and requirements below.
Do not allow the products of combustion to accumulate in any space or enclosure
OUTDOOR / PATIO Installation:
This heater is certified for use on outdoor patio's in accordance with ANSI Z83.26 / CSA
2.37 . Schwank warrants that the heater will operate as designed in mild wind conditions
up to 10 MPH. Note this unit is not designed to operate in adverse weather conditions
including higher wind speeds exceeding the certification requirement of 10 MPH.
What is "Outdoor"?:
An appliance approved for "outdoor use" may be installed with shelter no more inclusive than:
With walls on all sides, but with no overhead cover, (overhead permanently open) or

Within a partial enclosure which includes an overhead cover and no more than two side

walls. These side walls may be parallel, as in a breezeway, or at right angle to each other.
The open sides must be permanently open or
Within a partial enclosure which includes an overhead cover and three side walls, as long

as 30 percent or more of the horizontal periphery of the enclosure is permanently open.
If these "outdoor" conditions are not met, the appliance is approved for "indoor use"
and ventilation requirements of local codes apply. See "Indoor Application" below.

INDOOR Installation:

This heater is certified for space or spot heating of commercial / industrial non-
residential indoor spaces in accordance with ANSI Z83.19b / CSA 2.35b.
Inadequate venting of a heater may result in asphyxiation, carbon monoxide poisoning, injury or death.
Heating system venting must be in accordance with all local, state, provincial, and national codes (ANSI
Z223.1/NFPA 54 in USA; B149.1 in Canada).
WARNING
INDOOR INSTALLATION IN A STRUCTURE THAT HAS NO INSULATION IN THE
ROOF CAN RESULT IN THE FORMATION OF CONDENSATION ON COLD SURFACES.
16
888-Warm-Glo
2100 / IO 100 Manual
IM110107
RD: SEPT 2016
R.L. 7

Advertisement

Table of Contents
loading

Table of Contents