Improper installation, adjustment, alteration, ser- vice or maintenance can cause property dam- age, injury or death. Read the installation, oper- ating and maintenance instructions thoroughly before installing or servicing this equipment. GP-MSJV-BX-07A STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
All local, provincial and national code require- The STV-JZ heater may be installed for heating of ments including the current latest edition B149.1 non-residential indoor spaces. It is beyond the INSTALLATION CODE”...
Page 6
The following tube lengths and corresponding BTU input ratings are available: TABLE 1 BTU/HR INPUT OVERALL APPROX NET MODEL HEATER LENGTH* WEIGHT IN LBS O’ TO 45OO’ ABOVE (FT) SEA LEVEL STV-JZ 155-60 155,000 59’ 8” STV-JZ 155-50 155,000 50’ 0” STV-JZ 130-50 130,000 50’ 0” STV-JZ 130-40 130,000 40’4”...
5. PRE-INSTALLATION SURVEY The STV-JZ heating system must have gas pip- Carefully survey area to be heated, and for best ing of the correct diameter, length, and arrange- results, whenever possible, place burner and ment to function properly. For this reason, a combustion chamber in coldest area.
7. SYSTEMS INCORPORATING 90 ELBOWS AND 180 ELBOWS The STV-JZ Series radiant tube heater can be The 90 elbows are shipped as a kit with one installed in configurations as illustrated in FIG- coupler, one reflector and one plate hanger, for URE 2.
FIGURE 3 MOUNTING BOTH PLATE HANGER TYPES Intermediate Webbed Hanger (note: cavity side always faces Burner). Use solid End Plate Hanger at Burner and Vent ends (note cavity side) GP-MSJV-BX-07A Page 7 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
Page 12
FIGURE 6 PLATE HANGER/ELBOW INSTALLATION JS-0508-JZ 4. Webbed Hanger Flange to mount UNDER 1. Webbed-Hanger the next Reflector 2. Reflectors 5. 90 Elbow (shown) 3. Webbed-Hanger Flange UNDER Reflector 6. Tube/Elbow Coupler GP-MSJV-BX-07A Page 8 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
Page 13
LOWER THAN VENT FIGURE 8 SUGGESTED MOUNTING HARDWARE EYE BOLT PIPE RING BEAM CLAMP BAR- E Y E THROUGH WITH OR CLEVIS JOIST SCREW HANGER EYE SCREW HOLE IN BEAM GP-MSJV-BX-07A Page 9 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
– in this location the hanger supports both tubes. c) Slide the Torctite coupler into position across the center of the joint d) IMPORTANT: TOURQUE THE COUPLER BOLTS TO 40 FT-LBS GP-MSJV-BX-07A Page 10 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
Page 15
THE SIDES OF THE BURNER PANEL FOR SERVICE OR RE- Secure suspension chain to eye PAIRS. hook in order to stabilize burner (SEE PRE-INSTALLATION SURVEY AND MOUNTING CLEAR- ANCES) GP-MSJV-BX-07A Page 11 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
Page 16
STV-JZ 110-50 not required STV-JZ 60-20 Where required the STV-JZ Series Heaters will be supplied with the turbulators NOTE: factory installed into the end tube(s) of the system configuration, and the tubes marked for easy identification on site. FIGURE 10 COUPLER 1.
URE 12 (PAGE 13), FIGURE 7(PAGE 9) Note that for both horizontal and angle mounting, the tube must be level along its length. Improper mounting can result in overheating of controls and combus- tible materials. Use only non-combustible mounting hardware. GP-MSJV-BX-07A Page 13 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
Page 18
NOTE: Except for the vent end plate hanger, all hangers must be installed with the cavity side facing the burner end of the system - the cavity side of the vent end hanger must face the vent GP-MSJV-BX-07A Page 14 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
5. Insert “S” hooks down from the top of the reflector extension 6. Rotate “S” hook approx. 90°, and insert into holes in reflector 7. Settle into place GP-MSJV-BX-07A Page 15 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
80' for STV-JZ Directly above a gas utility meter or service 155 and 130, and 50' for STV-JZ 110, 80 and 60. regulator. Total maximum allowable combined vent and Twelve inches from combustion air inlet ...
Page 22
12. COMBUSTION AIR DUCT Where heater is operated in a negative air condi- 130, and 50' for STV-JZ 110, 80 and 60. Neither tion or in contaminated air atmosphere such as the individual flue vent or combustion air duct is woodworking shops, air for combustion must be to exceed 50'.
If a rigid gas pipe connection is made, then compensation for normal gas supply pipe expansion, and radiant tube expansion must be provided. All piping must conform to local codes. SEE SECTION 14: ( PAGE 21) HEATER EXPANSION GP-MSJV-BX-07A Page 19 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
Page 24
When checking or setting the pressure. PLEASE SEE NEXT SECTION ON the manifold pressure, a water manometer HEATER EXPANSION. should used. Gauges which measure in GP-MSJV-BX-07A Page 20 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
20 ft / 30 ft / 40 ft / 50 ft 110,000 2” 30 ft / 40 ft / 50 ft 130,000 2” 40 ft / 50 ft / 60 ft 155,00 2 1/2” GP-MSJV-BX-07A Page 21 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
Electrical Code. ANSi/NFPA 70 or current Canadian Electrical Code. 16. HIGH ALTITUDE INSTALLATIONS Canada: All of the STV-JZ radiant tube heaters USA: If a heater is to be installed at altitudes are approved for altitudes zero to 4500 feet above above 2000 ft, the input must be reduced by 4% sea level and do not require de-rating.
WARRANTY. FOR ADDITIONAL INFORMATION, CONTACT YOUR LOCAL DISTRIBU- TOR OR MANUFACTURER. 19. SEQUENCE OF OPERATION - HONEYWELL S87J1034 STV-JZ Burner with direct spark ignition, is as follows : options #1 #2 Option #1: (120 volts) Once the flame sensor determines that ...
CERAMIC INSULATOR AND C A P, A N D CORRECT →CHECK BOOT OF THE IGNITION CABLE FOR SIGNS OF MELTING OR BUCKLING →TAKE PROTECTIVE ACTION TO SHIELD CABLE AND BOOT FROM EXCESSIVE cont’d TEMPERATURES GP-MSJV-BX-07A Page 25 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
Page 30
CALL FOR HEAT ENDS: CONTROLLER OPERATIONS →REMOVE VALVE LEAD AIR IGNITION CONTROL, IF SYSTEM SHUTS OFF VALVE CLOSES, RECHECK TEMPERATURE CONTROLLER AND WIRING, IF NOT, REPLACE GAS CONTROL OPERATOR TROUBLESHOOTING ENDS GP-MSJV-BX-07A Page 26 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
GROUND PRONG/PIN ONLY! DO NOT BEND THE IGNITER PRONG!!!! 1/4” The black bars located at the lower right corner can be used as a guide for adjustment. GP-MSJV-BX-07A Page 27 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
Observe Burner rating sure and gas line/ plate for the correct gas pressure, and check it with a manometer. If gas pressure is OK check line and orifice for obstructions. GP-MSJV-BX-07A Page 28 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
A CONTRACTOR IS CALLING FOR TECHNICAL SUPPORT, MUST PROVIDE THE FOLLOWING INFORMATION FROM HIS COMPLETED COMMISSIONING REPORT ON NEXT PAGE FAX COMPLETED FORM TO TECHNICAL SERVICES: CANADA - 905-712-8336 USA - 706-554-9390 GP-MSJV-BX-07A Page 29 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
Page 34
IF INSTALLED..IS TURBULATOR AT FLUE END OF SYSTEM THIS HEATER MUST HAVE GOOD ELECTRICAL GROUNDING * FAX COMPLETED FORM TO TECHNICAL SERVICES: CANADA - 905-712-8336 OR USA - 706-554-9390 GP-MSJV-BX-07A Page 30 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
Page 36
1/2” x 36” Hose 1/2” MPT x 1/2” MPT JL-0771-RB 175 to 200,00 Btuh, JL-0771-RB 3/4” x 36” Hose 1/2” MPT x 3/4” MPT JS-0532-SE Fresh Air Intake Adapter GP-MSJV-BX-07A Page 32 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
Page 37
Single heater per Thermostat for JS-0568-KT field mounting Burner housings Low Voltage Thermostat JS-0569-XX (24 Volts) 24 Volt Option: Multiple Heaters per Thermostat JM-0303 –KT ( for field mounting. in burner housing) GP-MSJV-BX-07A Page 33 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
Page 38
Touch Up Paint - JA-0587-XX High Temp, 369g aerosol can Side Reflector Extension Kit- JS-0509-KT l0” deep, l0 ft long Each Tube Protection Screen -5 feet long JA-0780-XX GP-MSJV-BX-07A Page 34 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
Reflector Cap for 90° Elbow 90° ELBOW REFLECTOR JA-0530-XX Vent cap 4" roof VENT CAP JA-0528-XX Horizontal wall 4" vent terminal VENT CAP Refer to Current Price List COMPLETE TUBE KIT GP-MSJV-BX-07A Page 39 STV-JZ Manual RD: MAR 2009 RL: 07A - BA...
LIMITED WARRANTY CERTIFICATE FOR GAS-FIRED INFRA-RED LOW INTENSITY TUBE HEATERS: STS-JZ / IQ, STV-JZ / IV, STW-JZ / IW, SPW-JZ / IWP & STR-JZ SERIES The Manufacturer warrants that this product is free from defects in material or workmanship under normal use and service subject to the terms of this document.