1.6 Wire ONE Unit to a Telco Line - Auto-Dialer

Connect to Incoming Telephone Company's
Phone Line
Locate the telephone company demarcation device.
IMPORTANT
Identify the telephone line that will connect to the Access Plus
unit and wire as shown.
Use only twisted pair telephone wire that is rated for direct underground
burial. DO NOT use wire that is intended for indoor applications.
Recommend Cat5e Gel Filled (flooded) UV Resistant Direct Burial Cable in
conduit. DO NOT run telephone wires and high voltage wires in the same
conduit. For complete info, see section 1.3.
Telephone
Locate unit's Phone Line
Company
Inside Device
Demarcation
Point
Tip
Ring
Tip
Ring
Tip
Ring
Central Office (C.O.)
TIP (+): White/blue mark
Demarcation Device
RING (-): Blue/white mark
Telco
Access Control Devices
"Normally Open"
Vehicular
Gate Operator
Use minimum 18
AWG wire for runs
up to 100 feet.
W A
R N
IN
G
MO
SER
VIN
16 AWG wire for
IOU
GA
G
TE
and
Oper
ate
S INJ
UR
CAN
free
of
gate
only
Y OR
CAU
or
Do
not
oper
allow
peop
le
and
when
gate
DEA
SE
Do
gate.
ate
child
obstr
area
TH
path
not
stand
ren
to
play
uctio
ns.
is
in
sight
Read
while
gate
in
gate
in
gate
owne
r's
is
path
movi
or
area
man
ual
ng.
walk
throu
and
safet
gh
y instr
uctio
ns.
CON
runs up to 200 feet.
ANS
MS
I/UL
FOR
CAN
CER
TO
-325
/CSA
ED
TIFI
C22
VEH
ICU
TO
.2
NO.
SS
CLA
LAR
GAT
247
53382
MOD
E OPE
EL
RAT
SER
IAL
HP
OR
VOL
TS
AMP
S
MAX
GAT
PHA
E LOA
SE
Door
King
D
60
Hz
, Inc.,
Ingle
woo
(Term. 11 and 13)
d,
CA
Pedestrian
Gate/Door
"Normally Close" with Maglock
(Terminal 15 and 16)
"Normally Open" with Electric Strike
(Terminal 14 and 16)
Magnetic locks or electric strikes must be
powered from a separate UL Listed power
transformer. DO NOT power strikes or magnetic
locks from the unit's power transformer. Use
minimum 18 AWG wire for runs up to 100 feet;
16 AWG wire for runs up to 200 feet. It is
recommended to keep power wire runs as short
as possible.
1810-162-A-6-16
Cat5e
Separate UL
Supplied Transformer
Listed Power
Transformer
Electric
Strike
The Access Plus system operates ONLY
on 16.5 VAC.
with 24 Volt transformer or source
voltage.
Use the supplied power
transformer, 16.5 VAC, 20 VA (or UL
listed equivalent) to power the
telephone entry system. DO NOT power
any other devices (electric strikes,
magnetic locks, additional units etc.)
from the unit's power transformer.
See section 1.4 for wire size and run
distances.
1877-010
PHONE LINE
INPUT
OUTPUT
TIP
RING GND GND
TIP RING
Telephone Line
(Twisted Pair)
For complete info,
see section 1.3.
Cat5e Without
Surge Board
Be sure to properly
ground ALL boards.
See section 1.5 for
acceptable
grounding sources.
Ground
12 AWG Min.
Cat5e
Polarity does not matter.
t
t p u
O u
C
V A
. 5
1 6
V A
2 0
DO NOT power the unit
OUT
OUT
GND
OUTPUT
LOW VOLTAGE LINE
Ground
12 AWG Min.
Within 3 ft
of Surge Board
1878-010
Optional Phone Line Surge Suppressor
DoorKing Surge Suppressor
P/N 1877-010 (or equivalent) is optional but
highly recommended.
For best protection, surge suppressor ground
wire MUST be 3-ft. or less in length. Use
minimum 12 AWG wire. Refer to instruction
sheet included with surge board and section
1.5 for complete information.
Check Polarity of Telephone Line
Check for polarity on the phone "IN" wires, terminals 1 and
2. Terminal 2 must be positive with respect to terminal 1. Set
a VOM meter to measure DC volts. Place the positive lead on
terminal 2 and the negative lead on terminal 1. If the meter
shows a positive voltage - OK. If the meter shows a negative
voltage (needle moves off scale to the left), reverse the wires
on terminals 1 and 2.
Main
Terminal
J1
J1
1
RING
Phone In
(1-2)
2
TIP
3
GND
4
5
6
7
1970-010
8
9
10
11
N.O.
Relay 1
Note: Each relay can control a
12
N.C.
(11-13)
normally open OR normally close
13
Com
access control device. Relay
14
N.O.
contacts are rated for 3 amps @
Relay 2
15
N.C.
30 VAC maximum.
(14-16)
16
Com
Power
17
16.5
VAC
18
(17-18)
OV
Access Plus System Circuit Board
Optional Low Voltage Surge Suppressor
DoorKing Surge Suppressor P/N 1878-010 (or
GND
IN
IN
equivalent) is optional but highly recommended.
INPUT
For best protection, surge suppressor ground wire
MUST be 3-ft. or less in length. Use minimum 12 AWG
wire. Refer to instruction sheet included with surge
board for complete information.