PVED-CL Controller for Electro-Hydraulic Steering, Version 1.38
Steering by Steering Wheel – Open Loop
Symbol
Magnetic valves off delay time
©
Danfoss | May 2016
consumption by the solenoid bridge in the PVED must be reduced or to remove a steering control
conflict between the OSP and the PVED.
The default value disables this functionality i.e. the magnetic valve bridge is enabled at all times.
Generally, the magnetic valve bridge is enabled when the PVED-CL receives a non-zero flow request.
Index
115
If Qm is set to 0, then the magnetic valve bridge will be disabled immediately when the SASA sensor is
the selected device.
Default
Value range
30 000
1 to 30 000 (ms)
11025583 | AQ00000216en-US0302 | 51