Powerware Prestige 6000 Installation And Operator's Manual page 88

Prestige series
Hide thumbs Also See for Prestige 6000:
Table of Contents

Advertisement

Service and Support
Pre-installation Planning
The UPS, when installed with a S/390 processor, will usually be placed
in a raised floor data center. A cable access will need to be cut in the
raised floor tile to allow for connection to customer power and the S/390
equipment. The following figures represent approximate dimensions of
cable access cuts for 3 standard raised floor tile sizes.
610 mm
24 in
The UPS can be positioned on the right side of the S/390 since S/390
growth adds frames to the left. A recommended distance between the
UPS is one floor tile.
80
Powerware
l
177 mm
127 mm
177 mm
l
(5 in)
(7 in
7 in)
or 600 mm
Tile
23.6 in
Raised Floor Tiles
Additional
< Frames
S/390
Front
®
Prestige Series Installation and Operator's Manual for IBM Applications (6000 VA) Uncontrolled Copy
l
177 mm
75 mm
177 mm
l
(3 in)
(7 in
7 in)
465 mm Tile
18.25 in
9910

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents