UPS with PPDM Startup

To start up the UPS:
Powerware
®
Prestige Series Installation and Operator's Manual for IBM Applications (6000 VA) Uncontrolled Copy
12. For the AS/400 interface, plug the AS/400 communications
cable into the serial port on the UPS rear panel. Plug the other
end of the cable into the J14 connector on your AS/400.
Specific locations of the J14 serial port are listed below
according to the AS/400 model:
:
AS/400 Models 3xx/5xx - located on the base power supply
on the back of the system unit
:
AS/400 Models 600/S10/620/S20 - on the power supply
:
AS/400 Models 640/S30/650/S40/SB1 - on the right side of the
regulator cage in the back of the tower
13. Start the UPS according to the following "UPS with PPDM
Startup" procedure.
1. If you are connecting the UPS to an AS/400, the QUPSDLYTIM
system value for the UPS Monitoring feature should be set. See
"UPS Monitoring" on page 50 for instructions.
2. Verify the PPDM input breaker is in the OFF (O) position (does
not apply to the IEC 309 PPDM).
3. Confirm the correct UPS output voltage is selected (see Step 5
on page 37).
4. Turn on the equipment that is connected to the UPS.
5. Confirm the Bypass switch on the PPDM rear panel is in the
NORMAL position.
6. Plug the input power supply cord into the utility input
receptacle on the PPDM rear panel.
7. Plug the other end of the power supply cord into a grounded,
three-wire, AC receptacle that has been wired in accordance
with NEC specifications or national wiring rules. See Chapter 6,
"Specifications" on page 65 for the input current/output voltage
requirements.
Installation
39