Troubleshooting Tips - Powerware Prestige 6000 Installation And Operator's Manual

Prestige series
Hide thumbs Also See for Prestige 6000:
Table of Contents

Advertisement

REPO
NOTE

Troubleshooting Tips

If you should encounter any problems during startup, see the
troubleshooting chart on page 71.
The battery cabinets are shipped with the batteries charged. However,
batteries may lose some of the charge during shipping and storage. You
can use the UPS immediately after unpacking, but it may not provide the
full-rated backup time during a power failure. Upon initial startup, the
UPS may need to operate for approximately 8 hours before the battery is
fully charged and full battery-backup time is available. If the Battery
Fault indicator flashes, operate the UPS for 24 hours to fully charge the
battery.
Powerware
®
Prestige Series Installation and Operator's Manual for IBM Applications (6000 VA) Uncontrolled Copy
Optional REPO Cord Junction Box Connections
Wire Function
L1
L2
Ground
The REPO function activates when L1 and L2 are shorted together.
Terminal
Terminal Wire Size
Position
Rating
TB1-4
12 - 22 AWG
TB1-5
(4 - 0 mm
(4 - 0 mm
TB1-6
Installation
Suggested Wire
Size
18 AWG (0.75 mm
(
2
2
)
)
2
)
)
43

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents