DAR
4.2.1.3 Voltage present during a continuity, resistance, or
capacitance measurement
4.2.1.4 Memory full (Model 6524)
MEM
4.2.2 Resetting the Instrument
You can reset your instrument at any time. To do this:
1. Press the ▲ and
2. Turn the rotary switch to any setting other than OFF.
3. The instrument reboots.
Megohmmeter Model 6522/6524
With the Model 6524, if this
condition occurs during a DAR or PI
measurement, the instrument interrupts
the measurement and displays the
screen shown to the left.
G
If during a continuity, resistance,
or capacitance measurement the
instrument detects an external
voltage in excess of 15V (AC or DC),
it interrupts the measurement and
displays the screen show to the left.
You must eliminate the voltage to
resume the measurement.
When the memory is full (300
recordings), the instrument displays
the screen shown to the left. You must
remove one or more recordings before
new recordings can be saved (see §
2.3.3).
buttons simultaneously.
41