Vega VEGAPULS 61 Operating Instructions Manual page 24

Radar sensor for continuous level measurement of liquids
Hide thumbs Also See for VEGAPULS 61:
Table of Contents

Advertisement

4 Mounting
Configuration bypass
Instructions and require-
ments, bypass
24
4
100 %
5
0 %
Fig. 18: Configuration bypass
1
Radar sensor
2
Polarisation marking
3
Instrument flange
4
Distance sensor reference plane to upper tube connection
5
Distance of the tube connections
6
Ball valve with complete opening
Instructions of orientation of the polarisation:
Note marking of the polarisation on the sensor
With threaded versions, the marking is on the hexagon, with flange
versions between two flange holes
The marking must be in one plane with the tube connections to the
vessel
Instructions for the measurement:
The 100 % point may not be above the upper tube connection to
the vessel
The 0 % point may not be below the lower tube connection to the
vessel
Min. distance, sensor reference plane to upper edge of upper tube
connection > 300 mm
During parameter adjustment, select "Application standpipe" and
enter the tube diameter to compensate for errors due to running
time shift
A false signal suppression with the installed sensor is recom-
mended but not mandatory
The measurement through a ball valve with unrestricted channel
is possible
1
2
3
VEGAPULS 61 • Foundation Fieldbus
6

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vegapuls 62Vegapuls 65

Table of Contents