Setup - Max. adjustment
Setup - Damping
Lock setup - adjustment
VEGAPULS 61 • Foundation Fieldbus
4. Enter the suitable distance value in m for the empty vessel (e.g.
distance from the sensor to the vessel bottom) corresponding to
the percentage value.
5. Save settings with [OK] and move with [ESC] and [->] to the max.
adjustment.
Proceed as follows:
1. Select with [->] the menu item Max. adjustment and confirm with
[OK].
2. Prepare the percentage value for editing with [OK] and set the
cursor to the requested position with [->].
3. Set the requested percentage value with [+] and save with [OK].
The cursor jumps now to the distance value.
4. Enter the appropriate distance value in m (corresponding to the
percentage value) for the full vessel. Keep in mind that the max.
level must lie below the min. distance to the antenna edge.
5. Save settings with [OK]
To damp process-dependent measured value fluctuations, set an
integration time of 0 ... 999 s in this menu item.
The default setting is a damping of 0 s.
In this menu item, the PIN is activated/deactivated permanently.
Entering a 4-digit PIN protects the sensor data against unauthorized
access and unintentional modifications. If the PIN is activated perma-
nently, it can be deactivated temporarily (i.e. for approx. 60 min.) in
any menu item.
6 Set up with the display and adjustment module