Vega VEGAPULS 61 Operating Instructions Manual page 41

Radar sensor for continuous level measurement of liquids
Hide thumbs Also See for VEGAPULS 61:
Table of Contents

Advertisement

VEGAPULS 61 • Foundation Fieldbus
Properties, sensor:
– Measurement speed optimized by virtually no averaging
– Sporadic false echoes are suppressed
– False signal suppression recommended
Standpipe:
Product speed: very fast filling and emptying
Vessel:
– Vent hole
– Joins like flanges, weld joints
– Shifting of the running time in the tube
Process/measurement conditions:
– Condensation
– Buildup
Properties, sensor:
– Measurement speed optimized through little averaging
– Entering the tube inside diameter takes the running time shift
into consideration
– Echo detection sensitivity reduced
Bypass:
Product speed:
– Fast up to slow filling with short up to long bypass tube possible
– Often the level is hold via a control facility
Vessel:
– Lateral outlets and inlets
– Joins like flanges, weld joints
– Shifting of the running time in the tube
Process/measurement conditions:
– Condensation
– Buildup
– Separation of oil and water possible
– Overfilling into the antenna possible
Properties, sensor:
– Measurement speed optimized through little averaging
– Entering the tube inside diameter takes the running time shift
into consideration
– Echo detection sensitivity reduced
– False signal suppression recommended
Plastic tank:
Vessel:
– Instrument fix mounted or built in
– Measurement through the vessel top, if appropriate to the
application
– With empty vessel, the measurement can go through the bot-
tom
Process/measurement conditions:
– Condensation on the plastic ceiling
– In outdoor facilities, water and snow on vessel top possible
Properties, sensor:
– False signals outside the vessel are not taken into consideration
– False signal suppression recommended
6 Set up with the display and adjustment module