Operating Instructions Manual as well as the Safety Manual that comes with instruments with SIL qualification. These manuals are available in the download area of "www.vega.com". Operating instructions VEGAPULS 61 - Profibus PA: Document- ID 28444 Editing status of the quick setup guide: 2018-02-16...
During work on and with the device the required personal protective equipment must always be worn. Appropriate use VEGAPULS 61 is a sensor for continuous level measurement. You can find detailed information about the area of application in chapter "Product description".
For operation inside of closed vessels, points a to f in annex E of EN 302372 must be fulfilled. FCC/IC conformity (only for USA/Canada) VEGAPULS sensors with all antenna versions are FCC/IC approved. VEGAPULS 61 • Profibus PA...
Modifications not expressly approved by VEGA will lead to expiry of the operating licence according to FCC/IC. VEGAPULS 61 is in conformity with part 15 of the FCC directives and fulfills the RSS-210 regulations. Note the corresponding regulations for operation: •...
Alternatively, you can access the data via your smartphone: • Download the VEGA Tools app from the "Apple App Store" or the "Google Play Store" • Scan the Data Matrix code on the type label of the instrument or •...
> 10 mm into the vessel > 200 mm (7.87") Fig. 1: Distance of the antenna to the vessel wall/vessel ceiling 2. Note min. socket diameter depending on the socket length For further information see chapter "Mounting". VEGAPULS 61 • Profibus PA...
11. Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable 12. Screw the housing lid back on The electrical connection is finished. VEGAPULS 61 • Profibus PA...
Wiring plan, double chamber housing The following illustrations apply to the non-Ex as well as to the Ex-ia version. Wiring plan I 2 C Fig. 4: Wiring plan - double chamber housing Voltage supply, signal output VEGAPULS 61 • Profibus PA...
Fig. 5: Insert display and adjustment module Note: If you intend to retrofit the instrument with a display and adjustment module for continuous measured value indication, a higher lid with an inspection glass is required. VEGAPULS 61 • Profibus PA...
The actual level is then calculated on the basis of these entered values. At the same time, the operating range of the sensor is limited from maximum range to the requested range. VEGAPULS 61 • Profibus PA...
Page 12
1. Move from the measured value display to the main menu by pushing [OK]. 2. Select the menu item "Service" with [->] and confirm with [OK]. Now the menu item "False signal suppression" is displayed. VEGAPULS 61 • Profibus PA...
1.000 m(d) 8.000 m(d) 2.000 m(d) Vessel form Linearisation curve Channel Damping ▼ Linear PV lin. value not known Sensor-TAG Sensor Display Basic adjustment ▶ Display Diagnostics Service Info Displayed value Backlight ▼ PA-Out Switched off VEGAPULS 61 • Profibus PA...
Page 14
Language Copy sensor data ▼ Copy sensor data? Enable? Deutsch Info Basic adjustment Display Diagnostics Service ▶ Info Instrument type Date of manufacture Last change using PC Sensor characteristics Software version Display now? Serial number VEGAPULS 61 • Profibus PA...
Ʋ Ex ia instrument 12 … 24 V DC Ʋ Ex-d-ia instrument Lighting not possible Power supply by DP/PA segment coupler Depending on the version M12 x 1, according to DIN 43650, Harting, 7/8" FF. VEGAPULS 61 • Profibus PA...
Page 16
6 Supplement Max. number of sensors non-Ex/Ex 32/10 VEGAPULS 61 • Profibus PA...