During work on and with the device the required personal protective equipment must always be worn. Appropriate use VEGAPULS 65 is a sensor for continuous level measurement. You can find detailed information about the area of application in chapter "Product description". Operational reliability is ensured only if the instrument is properly used according to the specifications in the operating instructions manual as well as possible supplementary instructions.
FCC ID: O6QPULS6566 • IC: 3892A-PS6566 Modifications not expressly approved by VEGA will lead to expiry of the operating licence according to FCC. VEGAPULS 65 is in conformity with part 15 of the FCC regulations. Take note of the respective operating regulations: • This device may not cause interference, and •...
That is why we have introduced an environment management system with the goal of continuously improving company environmental pro- tection. The environment management system is certified according to DIN EN ISO 14001. Please help us fulfil this obligation by observing the environmental instructions in this manual: • Chapter "Packaging, transport and storage" • Chapter "Disposal" VEGAPULS 65 • 4 … 20 mA/HART - four-wire...
"VEGA Tools" and "Instrument search". You can find the serial number on the inside of the instrument as well as on the type label on the outside. Alternatively, you can access the data via your smartphone: • Download the smartphone app "VEGA Tools" from the "Apple App Store" or the "Google Play Store" • Scan the Data Matrix code on the type label of the instrument or •...
> 500 mm (19.69") Fig. 1: Distance of the antenna to the vessel wall/vessel ceiling 2. Note min. socket diameter depending on the socket length For further information see chapter "Mounting". VEGAPULS 65 • 4 … 20 mA/HART - four-wire...
10. Connect the screen to the internal ground terminal, connect the external ground terminal to potential equalisation 11. Tighten the compression nut of the cable entry gland. The seal ring must completely encircle the cable 12. Screw the housing lid back on The electrical connection is finished. VEGAPULS 65 • 4 … 20 mA/HART - four-wire...
4 Connecting to power supply Wiring plan, double chamber housing The following illustrations apply to the non-Ex and also to the Ex-ia version. Wiring plan 4...20mA L1 N 4 ... 20 mA Fig. 3: Wiring plan, double chamber housing Voltage supply Signal output VEGAPULS 65 • 4 … 20 mA/HART - four-wire...
The display and adjustment module is powered by the sensor, an ad- ditional connection is not necessary. Fig. 4: Insert display and adjustment module Note: If you intend to retrofit the instrument with a display and adjustment module for continuous measured value indication, a higher lid with an inspection glass is required. VEGAPULS 65 • 4 … 20 mA/HART - four-wire...
The radar sensor measures the distance from the sensor to the product surface. For indication of the real level, an allocation of the measured distance to the percentage height must be carried out. VEGAPULS 65 • 4 … 20 mA/HART - four-wire...
Page 12
The radar sensor measures the distance from the sensor to the product surface. For indication of the real level, an allocation of the measured distance to the percentage height must be carried out. VEGAPULS 65 • 4 … 20 mA/HART - four-wire...
These settings can be made ahead of time without the instrument having to be installed. Menu schematic Information: Depending on the version and application, the light-coloured menu windows are not always available or offer nor selection possibility. VEGAPULS 65 • 4 … 20 mA/HART - four-wire...
Basic adjustment Display ▶ Diagnostics Service Info Peak value indicator Meas. certainty Curve selection Echo curve 15 dB ▼ Distance min.: 0.234 m(d) Sensor status Presentation of the echo Echo curve curve Distance max.: 5.385 m(d) VEGAPULS 65 • 4 … 20 mA/HART - four-wire...
Page 15
Basic adjustment Display Diagnostics Service ▶ Info Instrument type Date of manufacture Last change using PC Sensor characteristics 22. November 2010 Software version Display now? Serial number 3.80 22. November 2010 12345678 VEGAPULS 65 • 4 … 20 mA/HART - four-wire...
Ʋ Double chamber housing – 1 x cable gland M20 x 1.5 (cable: ø 5 … 9 mm), 1 x blind plug M20 x 1.5; plug M12 x 1 for VEGADIS 61 (optional) – 1 x closing cap ½ NPT, 1 x blind plug ½ NPT, plug M12 x 1 for VEGADIS 61 (optional) – 1 x plug (depending on the version), 1 x blind plug M20 x 1.5; plug M12 x 1 for VEGADIS 61 (optional) Spring-loaded terminals for wire cross- < 2.5 mm² (AWG 14) section Voltage supply Operating voltage Ʋ Non-Ex and Ex-d instrument 20 … 72 V DC, 20 … 253 V AC, 50/60 Hz Max. power consumption 4 VA; 2.1 W VEGAPULS 65 • 4 … 20 mA/HART - four-wire...