Diagnostics - Echo curve
memory
Additional adjustments -
Device units
Additional adjustments -
Unit SV2
Additional adjustments -
False signal suppression
VEGAPULS 61 • Foundation Fieldbus
"Y-Zoom": 1, 2, 5 and 10x signal magnification in "dB"
"Unzoom": Reset the presentation to the nominal measuring range
without magnification
With the function "Echo curve memory" the echo curve can be saved
at the time of setup. This is generally recommended; for using the As-
set Management functions it is absolutely necessary. If possible, the
curve should be saved with a low level in the vessel.
With the adjustment software PACTware and the PC, the high resolu-
tion echo curve can be displayed and used to recognize signal
changes over the operating time. In addition, the echo curve of the
setup can be also displayed in the echo curve window and compared
with the actual echo curve.
Additional adjustments
In this menu item you select the measured variable of the system and
the temperature unit.
In this menu item, you define the unit of the Secondary Values 2
(SV2):
The following circumstances cause interfering reflections and can
influence the measurement:
High sockets
Vessel installations such as struts
Agitators
Buildup or welded joints on vessel walls
Note:
A false signal suppression detects, marks and saves these false
signals so that they are no longer taken into account in the level
measurement.
6 Set up with the display and adjustment module
49