6.1 Overview

Introduction
This section describes the field calibration procedures for Input 1.
• Every
UDC
factory-calibrated and ready for configuration to range by the user.
• However, these procedures can be implemented if the factory calibration of the
desired range is not within specification.
FIELD CALIBRATION WILL BE LOST
The field calibration will be lost if a change in input type configuration is implemented at a later time. The
original factory calibration data remains available for later use after a field calibration is done. See
subsection 6.6 if you want to restore factory calibration.
What's in this section?
The following topics are covered in this section.
6.1 Overview
6.2 Minimum and Maximum Range Values
6.3 Preliminary Information
6.4 Input #1 Set Up Wiring
6.5 Input #1 Calibration Procedure
6.6 Restore Factory Calibration
INPUT CALIBRATION MAY REQUIRE ACCESS TO HAZARDOUS LIVE CIRCUITS, AND
SHOULD ONLY BE PERFORMED BY QUALIFIED SERVICE PERSONNEL. MORE THAN
ONE SWITCH MAY BE REQUIRED TO DE-ENERGIZE UNIT BEFORE CALIBRATION.
Failure to comply with these instructions could result in death or serious injury.
1/01

6 Input Calibration

2300 Limit controller contains all input actuation ranges, which are fully
TOPIC
WARNING—SHOCK HAZARD
UDC2300 Limit Controller Product Manual
Input Calibration
See Page
43
44
45
47
49
51
!
43